CS1D-IC102D Omron, CS1D-IC102D Datasheet - Page 205

no-image

CS1D-IC102D

Manufacturer Part Number
CS1D-IC102D
Description
CS1D Dual IO Control Unit
Manufacturer
Omron
Datasheet

Specifications of CS1D-IC102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Wiring Methods
DC Power Supply Models
CS1D-PD024/025 Power Supply Unit
DC Power Source
Power Supply Capacity
Wiring
170
!Caution Tighten the AC power supply terminal block screws to the torque of 0.8 N m.
Note
Note Do not remove the protective label from the top of the Unit until wiring has
Loose screws may result in short-circuit, malfunction, or fire.
1. Be sure to check the setting of the voltage selector before supplying power.
2. Always remove the label from the top of the Power Supply Unit after wiring
been completed. This label prevents wire strands and other foreign matter
from entering the Unit during wiring procedures. Do not forget to remove the
label from the top of the Unit after wiring the Unit. The label will block air circu-
lation needed for cooling.
Supply 24 V DC. Keep voltage fluctuations within the specified range (19.2 to
28.8 V DC).
The maximum power consumption is 40 W per Rack for the CS1D-PD024 and
60 W per Rack for the CS1D-PD025, but there will be a surge current of about
five times that level when the power is turned ON.
POWER
Terminal screws
Recommended wire size
Recommended tightening
torque
the Unit. The label will block air circulation needed for cooling.
NC
NC
NC
NC
PD024
L2/N
L1
DC24V
M3.5 self-raising terminals
M3.5 self-rising screws
AWG 20 to 14 (0.517 to 2.08 mm
0.8 N·m
2
)
DC power source
Section 5-4

Related parts for CS1D-IC102D