CS1D-IC102D Omron, CS1D-IC102D Datasheet - Page 297

no-image

CS1D-IC102D

Manufacturer Part Number
CS1D-IC102D
Description
CS1D Dual IO Control Unit
Manufacturer
Omron
Datasheet

Specifications of CS1D-IC102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Immediate Refreshing
(Single CPU Systems
Only)
262
I/O Area
1,2,3...
Note Immediate refreshing will be performed for input bits allocated to Basic I/O
In the following example, CIO 000101 is allocated to switch 1, an external
switch connected to the input terminal of an Input Unit. The ON/OFF status of
switch 1 is reflected in CIO 000101 once each cycle.
When the immediate refreshing variation of an instruction is specified by
inputting an exclamation point just before the instruction, and the instruction’s
operand is an input bit or word, the word containing the bit or the word itself
will be refreshed just before the instruction is executed. This immediate
refreshing is performed in addition to the normal I/O refreshing performed
once each cycle.
Units only (excluding C200H Group-2 High-density I/O Units and Basic I/O
Units mounted in Remote I/O Slave Racks), not High-density I/O Units which
are Special I/O Units.
1. Bit Operand
2. Word Operand
In the following example, CIO 000101 is allocated to switch 1, an external
switch connected to the input terminal of an Input Unit. The ON/OFF status of
switch 1 is read and reflected in CIO 000101 just before !LD 000101 is exe-
cuted.
Just before the instruction is executed, the ON/OFF status of the 16 I/O
points allocated to the word containing the specified bit will be read to the
PLC.
Just before the instruction is executed, the ON/OFF status of the 16 I/O
points allocated to the specified word will be read to the PLC.
Switch 1
Input Unit
Ladder symbol
000101
Once
each
cycle
CPU Unit
Bit allocation
LD 000101
Mnemonic
CIO 000101
Section 8-3

Related parts for CS1D-IC102D