CS1D-IC102D Omron, CS1D-IC102D Datasheet - Page 551

no-image

CS1D-IC102D

Manufacturer Part Number
CS1D-IC102D
Description
CS1D Dual IO Control Unit
Manufacturer
Omron
Datasheet

Specifications of CS1D-IC102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
516
Auxiliary Area Allocations
A317
A319
Words
Address
Duplex Verification Errors (Duplex CPU Systems only)
(When A31600 turns ON, the cause of the error will be indicated here.)
A31706
A31707
A31708
A31710
A31713
A31714
A31715
Error Power Supply Unit Location
When an error in a Power Supply Unit results in an error in the 5-V/26-V output, one of the following bits will turn ON to show
the location of the Power Supply Unit with the error. A31602 (Duplex Power Supply Unit Error Flag) can be used to determine
if there is an error and the following bits can be used to locate the error.
A31900
A31901
A31902
A31903
A31904
A31905
A31906
A31907
A31908
A31909
A31910
A31911
A31912
A31913
A31914
A31915
Bits
Other CPU
Unit
Duplex
Verifica-
tion Error
Flag
(Duplex
CPU Sys-
tem only)
CPU Unit
Model Ver-
ification
Error Flag
CPU Unit
Version
Verifica-
tion Error
Flag
Inner
Board
Model Ver-
ification
Error Flag
Parameter
Area Veri-
fication
Error Flag
No Active
CPU Unit
Error Flag
(Duplex
CPU Sys-
tem only)
User Pro-
gram Veri-
fication
Error Flag
Right Power Supply Unit on CPU Rack (Rack 0)
Left Power Supply Unit on CPU Rack (Rack 0)
Right Power Supply Unit on CPU Rack (Rack 1)
Left Power Supply Unit on CPU Rack (Rack 1)
Right Power Supply Unit on CPU Rack (Rack 2)
Left Power Supply Unit on CPU Rack (Rack 2)
Right Power Supply Unit on CPU Rack (Rack 3)
Left Power Supply Unit on CPU Rack (Rack 3)
Right Power Supply Unit on CPU Rack (Rack 4)
Left Power Supply Unit on CPU Rack (Rack 4)
Right Power Supply Unit on CPU Rack (Rack 5)
Left Power Supply Unit on CPU Rack (Rack 5)
Right Power Supply Unit on CPU Rack (Rack 6)
Left Power Supply Unit on CPU Rack (Rack 6)
Right Power Supply Unit on CPU Rack (Rack 7)
Left Power Supply Unit on CPU Rack (Rack 7)
Name
ON: A duplex error occurred in the
other CPU Unit when entering
Duplex Mode. The “other CPU Unit”
indicates the standby CPU Unit for
the active CPU Unit and the active
CPU Unit for the standby CPU Unit.
ON: The CPU Units were not the
same model when entering Duplex
Mode.
ON: The unit version of the standby
CPU Unit is earlier than the unit ver-
sion of the active CPU Unit and the
active CPU Unit uses function not
supported by the standby CPU Unit.
ON: The duplex Inner Boards in the
two Process-control CPU Units were
not the same model when entering
Duplex Mode.
ON: The parameter area in the two
CPU Units in duplex mode do not
have the same contents.
ON: There is no active CPU Unit for
CPU Unit set for standby operation
when power was turned ON in
duplex mode. This occurs when one
of the following is detected: The
active CPU Unit is not mounted, the
CPU Unit switch is set to NO USE,
or pin 7 on the DIP switch is set for
simple backup operation.
ON: The user program in the two
CPU Units in duplex mode do not
have the same contents.
Function
ON: Verification
error
OFF: Normal
ON: Verification
error
OFF: Normal
ON: Verification
error
OFF: Normal
ON: Verification
error
OFF: Normal
ON: Verification
error
OFF: Normal
ON: No active
CPU Unit
OFF: Normal
ON: Verification
error
OFF: Normal
ON: Power Sup-
ply Unit error
OFF: Normal
Settings
Cleared
Cleared
Cleared
Cleared
Cleared
change
Status
mode
after
Cleared
Cleared
Cleared
Cleared
Cleared
Status at
startup
When
error
occurs
When
error
occurs
When
power is
turned ON
When
error
occurs
When
error
occurs
Timing
Appendix B
A31600
A31602
settings
Related
flags,