CS1D-IC102D Omron, CS1D-IC102D Datasheet - Page 477

no-image

CS1D-IC102D

Manufacturer Part Number
CS1D-IC102D
Description
CS1D Dual IO Control Unit
Manufacturer
Omron
Datasheet

Specifications of CS1D-IC102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Online Replacement of I/O Units, Special I/O Units, and CPU Bus Units
11-4-4 Online Replacement Precautions for Special I/O and CPU Bus
442
Units
!Caution Before replacing a Unit online, always disable the operation of all connected
!Caution If an Output Unit is replaced and ON status is held in memory for that Unit, the
!Caution If the settings in the new Unit are not the same as those in the Unit that was
Special I/O Units and CPU Bus Units have hardware switches, software
switches, and parameters, all of which help to control Unit operation. When a
Unit is replaced, all of these must be set to the same status as the Unit that
was replaced.
The specific settings that must be set depend on the type of Unit that is being
used. Refer to the operation manual for the specific Unit for details on these
settings.
external devices before starting the replacement procedure. Unexpected out-
puts from the Unit being replaced may result in unexpected operation of con-
trolled devices or systems.
corresponding output will turn ON as soon as the online replacement opera-
tion has been completed. Confirm system safety in advance.
replaced, unexpected operation may result possibly causing an accident.
Replace a Unit only after making sure that all settings are the same.
Refer to the operation manual of the specific Unit for details on any Units not
listed in the following tables and follow all replacements provided in the man-
ual.