Error Processing
Other Errors
10-2-5 Error Codes
406
Power Supply Unit
CPU Unit
Power Supply Unit
CPU Unit
POWER
RUN
ERR/ALM
INH
PRPHL
COMM
POWER
RUN
ERR/ALM
INH
PRPHL
COMM
Lit green.
Lit green.
---
---
Not lit.
---
Lit green.
Lit green.
---
---
---
Not lit.
The following table list error in order of severity, with the most serious error
given first. When more than one error occurs at the same time, the most seri-
ous error code will be stored in A400.
Rank
1
2
3
4
5
6
7
8
9
10
11
12
13
----
----
Auxiliary
flags in
Error
Area
Memory error
I/O bus errors
Duplicated
number errors
Too many I/O
points
I/O setting error I/O SET ERR
Program error
Cycle time
overrun error
FALS execution SYS FAIL FALS
Duplex verifica-
tion error
Duplex bus
error
Duplex power
error
Duplex commu-
nications error
Error
----
----
A400)
Error
code
(in
----
----
Flags
word
MEMORY ERR
I/O BUS ERR
(See note 1.)
I/O BUS ERR B
I/O BUS ERR C
UNIT NO. DPL ERR
RACK NO. DPL ERR
TOO MANY I/O PNT
PROGRAM ERR
CYCLE TIME ERR
(See note 2.)
DPL VERIFY ERR
(See note 6.)
DPL BUS ERR
(See note 6.)
PS ERR x-y
(See note 3.)
NET DPL ERR
(See note 4.)
data
and
Console display
Programming
Peripheral
Port Com-
munica-
tions Error
RS-232C
Port Com-
munica-
tions Error
Error
*
*
***
A communica-
tions error has
occurred in com-
munications with
the device con-
nected to the
peripheral port if
the indicators
have the status
shown at the left.
A communica-
tions error has
occurred in com-
munications with
the device con-
nected to the RS-
232C port if the
indicators have
the status shown
at the left.
Probable cause
A40115
Memory Error Flag
A40114
I/O Bus Error Flag
A40113
Duplicated Number Flag
A40111
Too Many I/O Points Flag
A40110
I/O Setting Error Flag
A40109
Program Error Flag
A40108
Cycle Time Overrun Flag
A40106
FALS Error Flag
A40214, A31600
A40214, A31601
A40214, A31602
A40214, A31603
Error flag
Check the PRPHL set-
ting on the Duplex Unit
or the DIP switch setting
on the CPU Unit and the
peripheral port settings
in the PLC Setup. Also
check the cable connec-
tions.
Check the COMM set-
ting on the Duplex Unit
or the DIP switch setting
on the CPU Unit, and
also the RS-232C port
settings in the PLC
Setup. Also check the
cable connections. If a
host computer is con-
nected, check the com-
munications settings of
the serial port on the
host computer and the
communications pro-
gram in the host com-
puter.
Possible remedy
Section 10-2
in A400
80F1
80C0 to
80C7,
80CF
80CC
80E9
80EA
80E1
80E0
80F0
809F
C101 to
C2FF
0011
0010
0003
0600 to
060F
stored
Code