Inputting, Modifying, and Checking the Program
4-6-4
54
Example
SBS UNDEFD
STEP OVER
SNXT OVER
STEP ERR
Message
Displaying the Cycle Time
A defined subroutine is not called by the main program. When this message is displayed because
of interrupt routine definition, there is no problem. In all other cases, correct the program.
STEP is used for more than 16 program sections. Correct the program to decrease the number of
sections to 16 or less. When the GPC is used the message “CPU WAITG” is displayed.
More than 48 SNTXs are used in the program. Correct the program to decrease the number to 48
or less.
STEP and SNXT are not correctly used. Correct the program.
Note Cycle time is displayed as scan time.
The following examples shows some of the displays that can appear as a
result of a program check.
Once the program has been cleared of syntax errors, the cycle time should
be checked. This is possible only in RUN or MONITOR mode while the pro-
gram is being executed. See Section 6 Program Execution Timing for details
on the cycle time.
To display the current average cycle time, press CLR then MONTR. The time
displayed by this operation is an average cycle time. The differences in dis-
played values depend on the execution conditions that exist when MONTR is
pressed.
Meaning and appropriate response
Check continues until END(01)
Halts program check
When errors are found
Display #1
Display
#2
Display
#3
Section 4-6