Specifications of F39-EU1E

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Light Curtain Type
Safety
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Main Modules with DC Solid-state Safety Output (E Modules)
Note: 1. With an inductive load, connect a diode or other surge absorber parallel to the load.
Relay Output Modules
R Modules: Delay time cannot be set.
R1 Modules: ON-delay can be set.
R2 Modules: OFF-delay can be set.
*1. An external fuse must be connected to the safety relay output. The safety category depends on the fuse rating:
*2. This rating is for Modules with built-in relays. The durability conditions are an ambient temperature of 15 to 35 C and an ambient humidity of
*3. This value is a reference value. The Modules are not designed to be used below this value. If a large load is applied even once, switching may
Rated Current
The rated current depends on the type and number of Modules used, as shown below.
Example:
F3SX-N-L2L2R: 150 (N Module) + 150 (L2 Module) + 150 (L2 Module) + 100 (R Module) = 550 mA
Input
DC solid-state output
Relay contact
outputs
Main Module (E, N)
Input Module (L1, L2, B1, D1)
Relay Output Module (R, R1, R2)
1)Safety Category 4 (EN954-1)
2) Safety Category 3 (EN954-1) or lower
25% to 75%.
not be possible for microloads.
A fuse rated at 3.15 A max. must be connected externally to protect the safety relay output from contact welding. The current that can be
applied to the relay contacts is limited by the fuse rating to 3.15 A max. (resistive load).
A fuse rated at 5 A max. must be connected externally to protect the safety relay output from contact welding. The current that can be applied
to the relay contacts is limited by the fuse rating to 5 A max. (resistive load). For details, refer to section 10.4.3.4 of prEN50156-1.
2. Except for voltage drop due to cable extension.
Module type
Number of main contacts (safety outputs)
Number of auxiliary contacts (auxiliary outputs)
Rated
load
Minimum permissible load *2
Electrical durability *2
Mechanical durability *2
http://www.ia.omron.com/
Emergency stop input
Reset input
Feedback input
Auxiliary input
DC solid-state safety output
Auxiliary solid-state output
Resistive
load
Inductive load
Item
Item
Terminals 11/12
Terminals 23/24
Terminals 33/34
(Main contacts: Safety outputs)
(Auxiliary contact: Auxiliary output)
Rated current
150 mA
150 mA
100 mA
ON: DC15 to 24 V 10%
OFF: Open or 0 to 5 VDC max.
Internal impedance: Approx. 5 k
PNP transistor output
Load current: 300 mA max. (resistance load/inductive load) *1
Residual voltage (when ON): 2 V max. *2
Residual voltage (when OFF): 0.1 V max.
Leakage current (when OFF): 0.1 mA max.
Allowable capacitive load: 1 F max.
Allowable wire resistance between output terminals and load: 4
PNP transistor output
Load current: 25 mA max; Residual voltage: 2 V max. *2
DPST-NO
SPST-NC
250 VAC, 50/60Hz, 30 VDC at 5A
250 VAC, 50/60Hz, 30 VDC at 3.15 A (5 A) *1
AC15: 240 VAC at 2 A cos = 0.3
DC13: 24 VDC at 1 A L/R = 48 ms
24 VDC at 5 mA (reference value) *3
100,000 operations min. (switching frequency: 1,800 times/hr)
10,000,000 operations min. (switching frequency: 36,000 times/hr)
(c)Copyright OMRON Corporation 2008 All Rights Reserved.
Ratings and Specifications
Ratings and Specifications
max.
F3SX
11