750-841 WAGO, 750-841 Datasheet - Page 119

no-image

750-841

Manufacturer Part Number
750-841
Description
CONTR.ETHERNET TCP/IP 10/100MBIT
Manufacturer
WAGO
Datasheet

Specifications of 750-841

Rohs Compliant
YES
No. Of Digital Inputs
10
No. Of Digital Outputs
10
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
Fig. 3.1-16:
After clearing a fault, restart the controller by cycling the power.
Fault message of the 'I/O' LED
1
2
3
Fault code 1: " Hardware and configuration fault "
Fault argument
st
nd
rd
blink sequence: Fault argument
blink sequence: Start of the Fault message
Coupler/Controller starts up
“I/O”-LED is shining
blink sequence: Fault code
“I/O”-LED is blinking
ready for operation
the power supply
Switching on
1
g012111e
Test o.k.?
Yes
Fault description
Overflow of the internal buffer
memory for the inline code
No
“I/O” LED
2nd flash sequence
Error code
(Number of flash cycles)
“I/O” LED
3rd flash sequence
Error argument
(Number of flash cycles)
“I/O” LED
1st flash sequence
(Introduction of the
error indication)
Signalling of the LED for indication of the node status
1st break
2nd break
Fieldbus Controller 750-841
Trouble shooting
Turn off the power supply of the
node, reduce number of I/O
modules and turn the power supply
on again. If the error still exists,
exchange the bus coupler.