216 •
5.2.4 Analog Output Modules
Process Data Architecture for MODBUS/TCP
Analog Output Modules
4 Channel Analog Input Modules
750-453, -455, -457, -459, -460, -468, (and all variations),
753-453, -455, -457, -459
The hardware of an analog output module has 16 bits of measured analog data
per channel and 8 bits of control/status. However, the coupler/controller with
MODBUS/TCP does not have access to the 8 control/status bits. Therefore,
the coupler/controller with MODBUS/TCP can only access the 16 bits of
analog data per channel, which are grouped as words and mapped in Intel
format in the Output Process Image.
When digital output modules are also present in the node, the analog output
data is always mapped into the Output Process Image in front of the digital
data.
2 Channel Analog Output Modules
750-550, -552, -554, -556, -560, -585, (and all variations),
753-550, -552, -554, -556
Offset
Offset
0
1
2
3
0
1
High Byte
High Byte
D1
D3
D5
D7
D1
D3
Byte Destination
Byte Destination
Low Byte
Output Process Image
Low Byte
Input Process Image
D0
D2
D4
D6
D0
D2
Measured Value Channel 1
Measured Value Channel 2
Measured Value Channel 3
Measured Value Channel 4
Output Value Channel 1
Output Value Channel 2
Remark
Remark
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP