1. To start the BootP server, click on the Start menu item Programs/WAGO
2. After the BootP Server is started, click on the Edit Bootptab button
program.
With the PFC program, this is possible in WAGO-I/O-PRO CAA using the
fuction block "ETHERNET_Set_Network_Config" of the library
„Ethernet.lib“.
The following describes how to allocate the IP address for a fieldbus node
using the WAGO BootP server by way of an example.
You can download a free copy of the WAGO’s BootP server over the Internet
under at http://www.wago.com/-
“Service“/“Downloads“/“Software“/“ELECTRONICC“/-
‘WAGO BootPServer V1.0 Windows 95/NT - ZIP Archiv‘.
BootP table
Fig. 3.1-12: BootP table
Note
The IP address can be allocated under other operating systems (e.g. under
Linux) as well as with any other BootP servers.
Attention
The IP address can be allocated in a direct connection via a crossover cable or
via a parallel cable and a hub. An allocation over a switch is not possible.
Note
A prerequisite for the following steps is the correct installation of the WAGO
BootP server.
Software/WAGO BootP Server.
located on the right hand side of the display. An editable file will appear in
Windows NotePad (bootptab.txt). This file is a database for the BootP
server. The file contains two examples for the allocation of an IP address,
the example commands are directly after the following comment lines:
- "Example of entry with no gateway"
- "Example of entry with gateway"
Fieldbus Controller 750-841
Fieldbus Controller
p012908d