750-841 WAGO, 750-841 Datasheet - Page 63

no-image

750-841

Manufacturer Part Number
750-841
Description
CONTR.ETHERNET TCP/IP 10/100MBIT
Manufacturer
WAGO
Datasheet

Specifications of 750-841

Rohs Compliant
YES
No. Of Digital Inputs
10
No. Of Digital Outputs
10
3.1.6 Data Exchange
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
The maximum number of simultaneous connections may not be exceeded. If
you wish to establish further connections, terminate an existing connection
first.
Data exchange takes place between the fieldbus master and the I/O modules,
between the PLC functionality of the controller and the I/O modules as well as
between the fieldbus master and the PLC functionality of the controller.
Currently, the 750-841 supports MODBUS/TCP and ETHERNET IP based
master devices. When the controller performs PLC functions, and controls
various I/O modules, this is done with the use of an IEC 61131-3 application
program, whereby the data addressing is different than the fieldbus addressing.
For data exchange, the ETHERNET TCP/IP fieldbus controller uses three main
interfaces:
The ETHERNET TCP/IP fieldbus controller can be configured for either
MODBUS/TCP or the Ethernet IP protocol.
MODBUS/TCP works according to the master/ model. The master (e.g., a PC
or a PLC) will query a slave device and the slave will return a response to the
master depending on the kind of query. Queries are addressed to a specific
node through the use of the IP address.
Typically, the ETHERNET TCP/IP controller of the WAGO-I/O-SYSTEM is
a slave device. But, with the use of the WAGO-I/O-PRO CAA programming
tool, the PFC can additionally perform master functions.
A controller is able to produce a defined number of simultaneous socket
connections to other network subscribers:
interface to the fieldbus (master),
the PLC functionality of the PFCs (CPU) and
the interface to the I/O Modules.
3 connections for HTTP (read HTML pages from the controller),
15 connections via MODBUS/TCP (read or write input and output data
from the controller),
128 Ethernet IP connections,
5 connections via the PFC (available for IEC 61131-3 application
programs)
2 connections for WAGO-I/O-PRO CAA (these connections are reserved
for debugging the application program via ETHERNET.
For debugging, WAGO-I/O-PRO CAA requires 2 connections at the same
time. However, only one programming tool can have access to the
controller.
10 connections for FTP
2 connections for SNMP
Fieldbus Controller 750-841
Fieldbus Controller