750-841 WAGO, 750-841 Datasheet - Page 45

no-image

750-841

Manufacturer Part Number
750-841
Description
CONTR.ETHERNET TCP/IP 10/100MBIT
Manufacturer
WAGO
Datasheet

Specifications of 750-841

Rohs Compliant
YES
No. Of Digital Inputs
10
No. Of Digital Outputs
10
2.8.3 Grounding Protection
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
For the field side, the ground wire is connected to the lowest connection
terminals of the power supply module. The ground connection is then
connected to the next module via the Power Jumper Contact (PJC). If the bus
module has the lower power jumper contact, then the ground wire connection
of the field devices can be directly connected to the lower connection
terminals of the bus module.
The ring feeding of the grounding potential will increase the system safety.
When one bus module is removed from the group, the grounding connection
will remain intact.
The ring feeding method has the grounding conductor connected to the
beginning and end of each potential group.
Fig. 2-24: Ring-feeding
Attention
Should the ground conductor connection of the power jumper contacts within
the node become disrupted, e.g. due to a 4-channel bus terminal, the ground
connection will need to be re-established.
Attention
The regulations relating to the place of assembly as well as the national
regulations for maintenance and inspection of the grounding protection must
be observed.
The WAGO-I/O-SYSTEM 750
Grounding
g0xxx07e
• 37