Specifications of LC1D18R7

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
440V
Relay Terminals
Screw Clamp
Width
45mm
Coil Resistance
2.24kohm
Nom Operating Power
10kW
External Width
45mm
Operating Voltage
600VAC
Switching Power Ac1
3hp
Switching Power Ac3
15hp
Switching Current Ac1
32A
Switching Current Ac3
18A
Load Current Inductive
18A
Load Current Resistive
32A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Characteristics of Type LC•K and LP•K Contactors
40
©
2001-2004 Schneider Electric All Rights Reserved
Pole Characteristics
Conventional thermal current (Ith) For ambient temperature
Rated operational frequency
Frequency limits of the
operational current
Rated operational voltage (Ve)
Rated making capacity
Rated breaking capacity
Permissible short-time rating
Short-circuit protection
Average impedance/pole
Utilization in category AC-1:
resistive circuit, heating, lighting
(Ve
Utilization in category AC-3
Squirrel cage motors
Utilization in category AC-3
Squirrel cage motors
440 V)
I rms conforming to NF C 63-110 and IEC 60947
LC K06, LPI K06, LC K09, LP K09
LC K12, LP K12
LC K16
Conforming to NF C 63-110 and IEC 60947
LC K06, LP K06, LC K09, LP K09 I rms
LC K12, LP K12
LC K16
In free air for a time "t” from cold state
(
LC K06, LP K06, LC K09, LP K09
LC K12, LP K12 LC K16
By circuit breaker
By fuses
At Ith and 50 Hz
At Ith and 60 Hz
Maximum rated operational current for a
temperature
Maximum rated operational current for a
temperature
Rated operational current limits in relation to
on-load factor and operating frequency
Increase in operational current by
paralleling of poles
Operational power
according to the voltage
LC K06, LP K06
LC K09, LP K09
LC K12, LP K12
LC K16
Maximum operating rate (in operating cycles/
hour in relation to percentage of rated power)
Operational power
according to the voltage
LC K06, LP K06
LC K09, LP K09
LC K12, LP K12
LC K16, LP K16
50 °C [122 °F])
50 °C (122 °F)
70 °C (158 °F)
50 °C (122 °F)
Voltage
50 or 60 Hz
Motor ratings
Motor ratings
Motor ratings
Motor ratings
Voltage
50 or 60 Hz
Motor ratings
Motor ratings
Motor ratings
Not UL Listed or CSA Certified.
20 A
50/60 Hz
Up to 400 Hz
690 Vac
110 A
144 A
160 A
220/
230 V
110 A
1 s
90 A
115 A
Select in accordance with NEC and local codes
Max 400% of motor FLA
3 m
3.6 m
20 A
16 A for Ve only
On-load factor
300 op. cycles/hour
120 op. cycles/hour
30 op. cycles/hour
Apply the following coefficients to the current values given
above. These take into account the often unbalanced current
distribution between poles
2 poles in parallel: K = 1.60
3 poles in parallel: K = 2.25
4 poles in parallel: K = 2.80
115 V
1-phase
0.37
kW
0.55
kW
Op. cycles/hour
Power
115
1-phase
0.5 HP
0.5 HP
0.5 HP
380/
400 V
5 s
85 A
105 A
220 V
0.75
kW
1.1 kW
220
1.5 HP
1.5 HP
110 A
1 HP
415 V
110 A
10 s
80 A
100 A
220/
240 V
3-phase
1.5 kW
2.2 kW
3 kW
4 kW
200/
208
3-phase
1.5 HP
2 HP
3 HP
440 V
110 A
110 A
110 A
30 s
60 A
75 A
90%
13 A
15 A
19 A
380/
415 V
2.2 kW
4 kW
5.5 kW
7.5 kW
220/
240
1.5 HP
3 HP
3 HP
500 V
80 A
80 A
80 A
1 min
45 A
55 A
60%
15 A
18 A
20 A
440/
480 V
4 kW
5.5/4
(480)
kW
5.5/4
(480)
kW
600
100%
460/
480
3 HP
5 HP
7.5 HP
3 kW
660/
690 V
70 A
70 A
70 A
3 min
40 A
50 A
30%
18 A
19 A
20 A
500/
600 V
3 kW
4 kW
4 kW
4 kW
900
75%
575/
600
3 HP
5 HP
10 HP
min
20 A
25 A
660/
690 V
3 kW
4 kW
4 kW
4 kW
1200
50%
01/04