M1PRF-4W 161-300VAC BROYCE CONTROL, M1PRF-4W 161-300VAC Datasheet

no-image

M1PRF-4W 161-300VAC

Manufacturer Part Number
M1PRF-4W 161-300VAC
Description
RELAY,SEQUENCE/LOSS, 3PHASE
Manufacturer
BROYCE CONTROL
Series
4-Wirer
Datasheet

Specifications of M1PRF-4W 161-300VAC

Contact Configuration
SPDT
Relay Mounting
DIN Rail
Contact Current Ac Max
8A
Contact Current Dc Max
8A
Contact Voltage Ac Max
250V
Contact Voltage Dc Max
25V
External Depth
59mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Applying power.
Note:
This device is not suitable for applications where there could be a percentage of re-generative voltage
present during a fault condition, i.e. fuse failure. During these conditions a monitor that includes an
adjustable under voltage trip level is necessary which allows this type of fault to be detected. It is therefore
recommended that the M1prt or M1prt-4w phase monitors be considered.
Troubleshooting.
The table below shows the status of the unit during a fault condition.
Type: M1PRF & M1PRF-4W
Phase Failure, Phase Sequence and Under Voltage
q
q
q
q
q
q
q
q
q
Supply fault
Phase or Neutral (4-wire only) missing
Phases reversed
Phase below 70% of Un (fixed under trip level)
Phase below 50% of Un
Telephone: +44 (0) 1902 773746 Facsimile: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: http://www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk.
(4-wire only) N
Fixed
Under trip
FUNCTION DIAGRAM
INSTALLATION AND SETTING
BEFORE INSTALLATION, ISOLATE THE SUPPLY.
Connect the unit as required. The diagram below shows a typical installation, whereby the supply to
the load is being monitored by the relay. If a fault should occur (i.e. fuse blowing), the contactor is de-
energised removing the 3-phase supply to the load. The contactor only re-energises after the fault has
cleared.
Apply power and the green “supply on” and red “relay” LED’s will illuminate, the relay will energise
and contacts 15 and 18 will close. Refer to the troubleshooting table if the unit fails to operate
correctly.
CONNECTION DIAGRAM
17.5mm DIN rail housing
Microprocessor controlled with internal monitoring (self-checking)
Monitors own supply and detects an Under voltage condition on one or more phases
M1PRF measures phase to phase voltage and M1PRF-4W measures phase to neutral voltage
Detects incorrect phase sequence, phase loss and neutral loss (4-wire only)
Fixed Under voltage trip level
Fixed time delay
1 x SPDT relay output 8A
Intelligent LED indication for supply and relay status
Monitored
3~ Supply
Output
L1, L2
L2, L3
L3, L1
L1
L2
L3
N*
Supply / Monitored
Local Fuse
Voltage
Hyst.
Td
Board
t
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England
t
Phase monitor
N*
Green LED
Off
Flashing
On
Off
L1
16 18
15
L2
L3
t
Red LED
Off
Off
Off
Off
Contactor
*N - Neutral connection
only available on 4-wire
version
Installation work must be carried
out by qualified personnel.
t
Phases reversed
Relay
De-energised
De-energised
De-energised
De-energised
LOAD
Td
Supply / monitoring
Frequency range:
Isolation:
Rated impulse
Power consumption:
(max.)
Trip level:
Voltage range:
Hysteresis:
Time delay (t):
Power on delay (Td):
Ambient temp:
Relative humidity:
Output (15, 16, 18):
Output rating:
Electrical life:
Dielectric voltage:
Rated impluse
Housing:
Weight:
Mounting option:
Terminal conductor size:
Approvals:
Options:
1. For other supply/monitoring voltages, please consult the sales office.
2. For alternative time delays or trip levels, please consult the sales office.
3. The unit is also available with a double-pole relay output. Refer to separate
data sheet for M3prf/2 and M3prf/2-4w.
voltage U*:
withstand voltage:
161 - 300V AC (3-wire)
withstand voltage:
77 - 143V AC (3-wire)
280 - 520V AC (3-wire)
44.5 - 82.5V AC (4-wire) 44.5V
93 - 173V AC (4-wire)
161 - 300V AC (4-wire)
surface mounting
TECHNICAL SPECIFICATION
MOUNTING DETAILS
Withdraw clips
fully when
Insert screwdriver
to release clips
M1PRF (L1, L2, L3)
77- 143V AC
161 - 300V AC
280 - 520V AC
48 - 63Hz
Over voltage cat. III
4kV (1.2 / 50 S) IEC 60664
L1: 20VA (3-wire), 13VA (4-wire)
L2: 0.2VA (3-wire), 0.1VA (4-wire)
L3: 20VA (3-wire), 0.1VA (4-wire)
Under trip level fixed at ( 2%):
77V
161V
280V
93V
161V
-20 to +60 C
+95%
SPDT relay
AC1
AC15
DC1
2kV AC (rms) IEC 60947-1
4kV (1.2 / 50 S) IEC 60664
Orange flame retardant UL94 VO
On to 35mm symmetric DIN rail to BS5584:1978
(EN50 002, DIN 46277-3) Or direct surface mounting via
2 x M3.5 or 4BA screws using the black clips provided on
the rear of the unit.
Conforms to IEC. CE and
to DIN 43880
2% of trip level (factory set)
100 mS (worst case = t x 2)
1sec. (worst case = Td x 2)
150,000 ops at rated load
70g
2 x 2.5mm
W. 17.5mm
Dims:
89 (excl. clips)
93 (+/- 1mm)
2
250V 8A (2000VA)
250V 5A (no), 3A (nc)
25V 8A (200W)
solid or stranded
45
M1PRF-4W (L1, L2, L3, N)
44.5 - 82.5V AC
93 - 173V AC
161 - 300V AC
Compliant.
Terminal Protection to IP20
voltage when ordering
Supply / monitoring
*Please state
49 59
M1PRF-3-A

Related parts for M1PRF-4W 161-300VAC