Communicating between OMRON PLCs
RECV(098)
138
(@)RECV(98)
S
D
C
S: Remote node beginning word
D: Local beginning word
C: First word of control data (below)
Note
C+1
C+2
C
15
15
15
The range of node addresses is different for networks other than Ethernet.
Remote node number M (send source)
00 to FE (Hex): 0 to 254
0001 to 03DE (Hex): 1 to 990 words
0
Number of reception words (m)
11
11
With the RECV(098) instruction, the data in m number of words, starting from
the beginning word S at the remote node (node address M) is received at the
words starting from the beginning word D at the local node.
The message services function does not guarantee that a message will reach
the destination node. A message may be lost during transmission due to fac-
tors such as noise. In order to prevent this from occurring when using mes-
sage services, it is common to set up retry processing at the node from which
instructions are issued. With the SEND(090), RECV(098), and CMND(490)
instructions, retry processing is executed automatically by specifying the num-
ber of retries, so specify a number other than 0.
0
8 7
8 7
Destination network number
00 (Hex):
01 to 7F (Hex): 1 to 127
Destination Unit address
00 (Hex):
10 to 1F: (Hex):
E1 (Hex):
FE (Hex):
0
0
0
Local network
D
m
15
CPU Unit
Unit #0 to #15
Inner Board
Unit connected to network
Local node
0
C+3
C+ 4
15
Response
0: Required.
1: Not required.
0
10
Number
of words
(m)
Remote node number N
8 7
Communications port number: 0 to 7
Response monitor time
0000 (Hex): 2 s
0001 to FFFF (Hex): 0.1 to 6,553.5 s
(in units of 0.1 s)
S
0
15
3
0
Number of retries
0 to F (Hex): 0 to 15 retries
0
Section 6-6