Network Relay Errors
8-6
Results Storage Area Response Codes
0003
0006
0009
000D
000E
0011
0016
0018
0020
003C
003D
003E
Response
code
Results Storage Area Response Codes
ESRCH
ENXIO
EBADF
EACCES
EFAULT
EEXIST
EINVAL
EMFILE
EPIPE
EPROTONO-
SUPPORT
EPROTOTYPE
ENOBUFS
UNIX error
message
No such process
No such device or address
Bad file number (incorrect socket
specification)
Permission denied
(Broadcast address specified for
remote IP address for active TCP
open)
Bad address (copy failed between
kernel and user area)
File exists
Invalid argument (socket library
argument error)
Too many open files (More than 32
sockets)
Broken pipe (remote node closed
socket)
Protocol not supported (protocol
other than UDP, TCP, or RAW speci-
fied)
Protocol wrong type for socket
No buffer space available
For network relay errors using SEND(090) or RECV(098), check the path of
the command using the routing tables and the nature of the error using the
response code to eliminate the cause of the error.
For network relay errors using CMND(490), the location of the relay error is
recorded in the second through third words of the response, as shown below.
The response codes stored in the Results Storage Area can be used to trou-
bleshoot socket service problems. Refer to Socket Services Parameter Area 1
to 8 (Ethernet Unit to CPU Unit) on page 88 for the location of the response
codes stored in the Results Storage Area.
The UNIX socket service error messages corresponding to the response
codes are given in the following table. Refer to the documentation for the
devices involved when communicating between an Ethernet Unit and other
devices.
Description
Second word
First word
Third word
Bit
Relay error flag
1
1
1
7
7
7
Main response code (MRES)
Error network address
6
6
6
5
5
5
First byte
4
4
4
3
3
3
2
2
2
Close the local socket and try reopening it.
Check the IP address of the remote node and
try to reconnect.
Close the local socket and try reopening it.
Close the local socket.
Close the local socket and try reopening it.
There is too much load (traffic) on the Ethernet
Unit. Check your user applications.
Command code
1
1
1
0
0
0
7
7
7
1: PLC fatal error flag
Error node address
6
6
6
S-b-response code (SRES)
1: PLC non-fatal error flag
5
5
5
Second byte
Probable remedy
4
4
4
3
3
3
2
2
2
1
1
1
0
0
0
Section 8-6
227