CV500ETN01 Omron, CV500ETN01 Datasheet - Page 170

no-image

CV500ETN01

Manufacturer Part Number
CV500ETN01
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500ETN01

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
6-6-5
Communicating between OMRON PLCs
(Continued on next page.)
Execution
condition (See note.)
120000
120000
000000
120001
120000
A20207 120002
A20207
A21907
Program Example
(See note.)
@MOV(21)
@MOV(21)
@MOV(21)
@MOV(21)
@MOV(21)
@XFER(70)
@SEND(90)
DIFU(13)
S
D00000
D00001
D00002
D00003
D00004
D00010
D00010
D00020
D00000
120001
120000
121000
KEEP
#000A
#000A
#0002
#0400
#0705
#0064
0000
R
When the Communications Port Enabled Flag for port 7
is ON, and RECV(098) is not being executed, the send
execution program will start when execution condition
CIO 000000 turns ON.
Control Data Creation
Send Data Creation
Input CIO 120000 remains ON from the start of
SEND(090) execution until completion.
D0000
D0001
D0002
D0003
D0004
Ten words of data from word CIO 0000 is
stored from D00010 onwards.
Word
Ten words of data from D00010 at the local node is
sent to D00020 onwards at network number 2, node
number 4, unit address 0 (the PLC).
Reset Input Creation
Send Error Display
Contents
00
00
04
07
00
0A
02
00
05
64
Number of send words = 10
Destination network number = 2
Destination node number = 4
Destination unit address = 0
Response required.
Communications port No. used = 7
Number of retries = 5
Response monitor time = 10 s
Meaning
Section 6-6
145

Related parts for CV500ETN01