7-3-22 IP ADDRESS WRITE
Command Block
Response Block
Command/Response Reference
Specify the IP address table records. The number of records specified must
be provided. The total number of bytes in the IP address table records is cal-
culated as the number of records
6 bytes of data in each record is as shown in the following diagram.
FINS Node Address
Node address for communications via the FINS command (hexadecimal).
IP Address
IP address used by TCP/IP protocol (hexadecimal).
The new I/O address table records will not be effective until the PC is
restarted or the Ethernet Unit is reset.
An error response will be returned if the IP address conversion method in the
system mode settings is set for automatic generation.
Write the local IP address and the subnet mask in the CPU Bus Unit System
Setup.
0000
1001
1002
1003
110C
2307
Command
Command
27 57
27 57
Response code
code
code
Response
code
IP address
Normal (echo reply received from the remote node)
Command too large
Command too small
The number of records specified does not match the sent data
length.
The number of records is not between 0 and 32.
The FINS node address is not between 1 and 126
The IP address is 0.
IP address conversion method is set for automatic generation.
FINS node
00
1
number
Subnet mask
6 bytes/record. The configuration of the
IP address
Description
6 bytes
Section 7-3
185