CV500-ZS3AT1-EV2 Omron, CV500-ZS3AT1-EV2 Datasheet - Page 47

no-image

CV500-ZS3AT1-EV2

Manufacturer Part Number
CV500-ZS3AT1-EV2
Description
C.V SOFTWARE 3.5in DISK
Manufacturer
Omron
Datasheet

Specifications of CV500-ZS3AT1-EV2

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Rack Number Switch
Peripheral Device
Connector
Rack Components
Display
2-3-4 Power Supply Units
34
Note Turn OFF the power to the PC before setting the rack number switches.
Note When connecting a Peripheral Device to the CPU or an I/O Interface Unit, set the
Note The total power consumed by each Rack must be within the values stated in the
Each Expansion I/O and Expansion CPU Rack is assigned a rack number from 1
through 7. Set the rack number on the rack number switch. Words are allocated
to Racks in order according to rack numbers, starting from the CPU Rack, which
is always rack number 0.
Set the rack number switch using a standard screwdriver. If a number other than
1 through 7 is assigned, or the same rack number is set to more than one Rack,
the PC will not operate
The display on the I/O Interface Unit is identical to that on the I/O Control Unit on
the CPU Rack. For details on the data displayed in each mode, refer to 2-3-2 I/O
Control Unit .
The I/O Interface Unit CV500-II201 for Expansion I/O Racks provides a connec-
tor for connecting a Peripheral Device. One Peripheral Device (CVSS or Pro-
gramming Console) can be connected per to the CPU or I/O Interface Units for
each PC, although additional Peripheral Devices can be connected to Slave
Racks if a SYSMAC BUS/2 System is used. Whether mounted to the CPU or an
I/O Interface Unit, the operation of the Peripheral Device is the same.
baud rate of the CPU to 50k bps via the CPU DIP switch.
The Power Supply Unit is available in three models. The CV500-PS221 and
CVM1-PA208 run on 100 to 120 VAC or 200 to 240 VAC, and the CV500-PS211
runs on 24 VDC. Both Power Supply Units can be used with any CPU Rack, Ex-
pansion CPU Rack, Expansion I/O Rack, or Remote I/O Slave Rack. The table
below summarizes the output capacity of the two models.
table above. For example, do not mount Units with a total current consumption
greater than 12 A to a Rack supplied by a 12-A Power Supply Unit.
CVM1-PA208
CV500-PS221
CV500-PS211
Model
100 to 120/200 to 240 VAC
24 VDC
Supply voltage
8 A at 5 VDC
12 A at 5 VDC
12 A at 5 VDC
Output power
Section 2-3

Related parts for CV500-ZS3AT1-EV2