Power Supply Units
Surge Current
3-4-2 Grounding
!
Caution
The surge current for the DC Power Supply Unit under maximum load conditions
is shown below. Consider the surge current characteristics when selecting the
power source, switches, breakers, etc.
Use crimp terminals for wiring. Do not connect bare stranded wires directly to
terminal blocks. Use M3.5 screws for tightening crimp terminals.
Tighten the screws on the terminal block to a torque of 0.8 N m.
Abide by the following precautions when wiring the Power Supply Units. Failure
to abide by these precautions my cause faulty operation or damage to the Unit.
The line ground (LG:
neutral terminal. Short the line ground terminal to the ground (GR:
improve noise resistance.
To avoid electrical shock, attach a grounded AWG 14 wire (cross-sectional area
of 2 mm
and must be checked periodically to be sure that environmental conditions have
not deteriorated ground capacity. Do not use a wire longer than 20 m.
7 mm max.
Electric
current
(A)
Input: 24 VDC; load: 12 A at 5 V (maximum load); ambient temp.: 25 C.
20 mm max.
Be sure that no wire clippings or other foreign materials enter the Units when
wiring.
Provide circuit breakers and other protective devices to protect the system
again external short circuits.
Check and recheck all wiring before supplying power to the system.
After wiring the terminals check the terminal block to be sure it is firmly locked
in place.
Tightening torque: 0.8 N m
2
) to the ground terminal. The ground resistance must be 100
) terminal of the Power Supply Unit is a noise-filtered
M3.5 screw
Time (ms)
7 mm max.
Section 3-4
) terminal to
or less
53