Power Supply Units
3-4-4 Emergency Stop
3-4-5 Power Interruptions
Power supply
Power interrup-
tion detection
signal
Program execution
Momentary Power
Interruption Flag
(A40202)
CPU reset signal
RUN output
85%
Shutdown processing
Power interruption
You can use an external relay (CR in the following figure) to form an emergency
stop circuit that shuts down the system when PC operation stops. This can be
achieved by wiring the RUN output from the Power Supply Unit on the CPU Rack
as shown below.
A sequence circuit is built into the PC to handle power interruptions. This circuit
prevents malfunctions due to momentary power loss or voltage drops. A timing
diagram for the operation of this circuit is shown below.
MCB1
*0.3 to 1 ms for DC power.
Normal
power interruption detection time: 10 to 25 ms*
MCB2
Standby
Stops
Power retention time: 10 ms (fixed)
Transformer
or noise filter
Twisted-pair wires
PC RUN
output
CR1
Momentary power inter-
ruption time (default: 0 ms)
Power OFF
interrupt program
CR1
Control section
Power supply
DC voltage
regulator
Surge suppressor
PC
Initialization
Power-ON
interrupt program
+
DC
input/output
Normal
Section 3-4
57