CV500-ZS3AT1-EV2 Omron, CV500-ZS3AT1-EV2 Datasheet - Page 68

no-image

CV500-ZS3AT1-EV2

Manufacturer Part Number
CV500-ZS3AT1-EV2
Description
C.V SOFTWARE 3.5in DISK
Manufacturer
Omron
Datasheet

Specifications of CV500-ZS3AT1-EV2

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Power Supply Units
3-4-3 Wiring Other Terminals
START Input
RUN Output
To system con-
trol circuits
Power supply
Emergency
stop circuit
Note
The Power Supply Units provide a START input and a RUN output. These termi-
nals can be used to help control system operation.
The START input terminals are short-circuited at the factory with a short bar. The
short bar can be removed and the terminals wired to a 10-mA, 24-VDC external
input to control PC operation. When these terminals are open, PC operation will
stop.
The RUN output terminals will be ON (closed) when the PC is operating in RUN
or MONITOR mode. These terminals can thus be wired to provide an external
signal indicating the operating status of the PC, such as is used in the emergen-
cy stop circuit in the next section.
1. Use reinforced insulation or double insulation on the DC power supply con-
2. The maximum switching capacity of the CV500-PS211 Power Supply Unit is
nected to CV500-PS211 Power Supply Unit when complying with EC direc-
tives (low voltage).
2 A at 24 VDC when complying with EC Directives (low-voltage directives).
START input (CPU Racks only)
24 V,10 mA
RUN output (all Racks)
Maximum Switching Capacity:
250 VAC: 2 A (resistive load, cosf = 1)
250 VAC: 0.5 A (inductive load, cosf = 0.4)
24 VDC: 2 A
Section 3-4
55

Related parts for CV500-ZS3AT1-EV2