Power Supply Units
3-4-1 Wiring the Power Source
AC Power Supply Units: CV500-PS221/CVM1-PA208
!
!
WARNING
Caution
Screw (3.5 mm head with
self-raising pressure plate)
Power Line
twisted-pair cable
(cross-sectional
area: 2 mm
Use AWG 14
The following diagrams show the proper way to connect the power source to the
Power Supply Unit. The terminals marked “NC” are not connected internally.
Use round crimp terminals for wiring. Do not connect bare stranded wires direct-
ly to terminal blocks. Use M3.5 screws for tightening crimp terminals.
Tighten the screws on the terminal block of the AC Power Supply Unit to a torque
of 0.8 N m. The loose screws may result in short-circuit, burning, or malfunc-
tion.
Do not allow your hands or any other part of your body, or any object in contact
with your body, to come into contact with the AC power supply section after
power has been turned on. Contact with the power supply section will result in a
dangerous or fatal electrical shock.
7 mm max.
20 mm max.
Tightening torque: 0.8 N m
2
min.
Isolation transformer
and ground can be signif-
icantly reduced by con-
necting a 1-to-1 isolation
transformer. Do not
ground the secondary
coil of the transformer.
1:1 isolation
transformer
Noise between the PC
M3.5 screw
Breaker
AC power source
200 to 240 VAC
tuations within the spe-
cified range (refer to
Appendix B Specifica -
tions )
Supply 100 to 120 or
Keep voltage fluc-
Section 3-4
51