5-4
5-4-1
AC Power Supply Models
Wiring Methods
POWER
Wiring Methods
Wiring Power Supply Units
Voltage selector
terminals
PA207R
L2/N
L1
100-120
CLOSE
200-240
OPEN
AC100V-120V/
AC2100-240V/
INPUT
RUN
OUTPUT
AC240V
DC24V
2A RESISTIVE
Note When 220 V AC power (200 to 240 V AC) is being supplied, be sure to
Note If 100 to 120 V AC power is supplied but the jumper bar has been removed to
Note The RUN output can be used from either the Power Supply Units on the CPU
CORRECT
Power
supply
AC power supply
Voltage selector:
Screws (3.5 mm head with
self-raising pressure plate)
Remove the short bar before applying 200 to 240 V AC.
Closed for 110 V AC
Open for 220 V AC
remove the jumper bar that shorts the voltage selector terminals. The Unit will
be damaged if 220 V AC is supplied with the jumper bar connected.
select 200 to 220 V AC, the Unit will not operate because the power supply
voltage will be below the 85% minimum level.
Rack or the Expansion Racks.
To obtain an output contact equivalent to RUN output when using a Power
Supply Unit without RUN output, use an output contact from the Power Supply
Unit with a constant ON flag as the input condition.
RUN output
ON when the CPU Unit is in RUN or MONITOR mode.
OFF when the CPU Unit is in PROGRAM mode or when a fatal error has occurred.
• Do not remove the protective label from the top of the Unit until wiring has
been completed. This label prevents wire strands and other foreign matter
from entering the Unit during wiring procedures.
220 V AC
power
Not connected
(OPEN)
Voltage selector
terminals
1:1 isolating
transformer
(Unit will be damaged.)
INCORRECT!
220 V AC
power
AC power source
100 to 200 V AC
200 to 240 V AC
Unit will be damaged
if connected.
Section 5-4