CS1W-MD292 24-V DC Input/Transistor Output Unit (48/48 Points, Sourcing)
Specifications of Basic I/O Units and High-density I/O Units
Outputs (CN1)
Rated Voltage
Operating Load Voltage
Range
Maximum Load Current
Maximum Inrush Cur-
rent
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Fuses
External Power Supply
Insulation Resistance
Dielectric Strength
Internal Current Con-
sumption
Weight
Accessories
Terminal Connections
The ERR indicator will light if a fuse blows or if the external power supply is turned OFF, and the
corresponding Flag in the Basic I/O Unit Information Area (A050 to A089) will turn ON.
12 to 24 V DC
10.2 to 26.4 V DC
0.1 A/point, 1.2 A/common,
3.6 A/Unit (See note 2.)
1.0 A/point, 10 ms max.
8.0 A/common, 10 ms max.
0.1 mA max.
1.5 V max.
0.5 ms max.
1.0 ms max.
48 points (16 points/common, 3
commons)
3 A (1 per common, 3 total)
The fuse cannot be replaced by
the user.
10.2 to 26.4 V DC, 50 mA min.
20 M between the external terminals and the GR terminal (100 V DC)
1,000 V AC between the external terminals and the GR terminal for 1 minute at a leakage cur-
rent of 10 mA max.
350 mA max. at 5 V DC
320 g max.
Two connectors for external wiring (soldered)
Refer to Figure 5.
When wiring, pay careful attention to the polarity. The load may operate if the polarity is
reversed.
Indicator
switch circuit
Blown fuse
detection
circuit
560
Output indicator
ERR indicator
1000 pF
4.7 k
SW
COM (+V)
OUT00
OUT15
0 V
IN00
IN15
COM
to
to
Inputs (CN2)
Rated Input Voltage
Allowable Input Voltage
Range
Input Impedance
Input Current
ON Voltage/ON Current
OFF Voltage/OFF Cur-
rent
ON Response Time
OFF Response Time
No. of Circuits
Number of Input Simul-
taneous ON
3 CN1 (Output)
3 CN2 (Input)
24 V DC
20.4 to 26.4 V DC
4.7 k
Approx. 5 mA (at 24 V DC)
17 V DC min./3 mA min.
5 V DC max./1 mA max.
8.0 ms max. (Possible to select
one out of eight times from 0 to
32 ms in the PLC Setup.) (See
note 1.)
8.0 ms max. (Possible to select
one out of eight times from 0 to
32 ms in the PLC Setup.) (See
note 1.)
48 points (16 points/common, 3
commons)
50% (8 points/common) (at 24 V
DC) (Depends on ambient tem-
perature.)
Appendix A