CS1D-BC042D Omron, CS1D-BC042D Datasheet - Page 282

no-image

CS1D-BC042D

Manufacturer Part Number
CS1D-BC042D
Description
CS1D Dual CPU Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-BC042D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Online Addition of Units and Backplanes
Maximum Number of Additional Units
7-7-2
Online Addition of Units
Online Addition Procedure
1,2,3...
Note As of October 2006, the online addition function is supported by CX-Program-
Note If the I/O table does not match, the online addition will not be executed.
When the Connecting Cables
are duplexed, all of the cables
must be connected properly
before adding a Rack.
Only 1 Unit can be added at a time. When multiple Units are being added, add
the Units one at a time.
Units and Backplanes can be added online only from the CX-Programmer’s
I/O Table Window; they cannot be added online from a Programming Console.
mer version 7.0 only when it has been added as an expansion function.
1. Mount the additional Unit in an empty slot.
2. Connect the CX-Programmer to the CPU Unit and go online.
3. Display the I/O Table Window. The I/O table will be matched to the PLC’s
4. Select Options - Online Add Unit - start. At this point, the CX-Program-
status. If the I/O table does not match, transfer the I/O table from the PLC
to the computer.
mer will check whether the I/O table matches the PLC configuration.
Units can be added in these slots starting from CIO 9.
The starting Rack word can also be set.
Special I/O Units can also be added.
Add a CS1W-AD0041 (unit
number 0) in Rack 1 slot 6.
Note: Always tighten the new Unit's
A Unit cannot be added to the
shaded slots because the word
address would be duplicated.
screws and verify that it is
secure.
Section 7-7
247

Related parts for CS1D-BC042D