CS1D-BC042D Omron, CS1D-BC042D Datasheet - Page 87

no-image

CS1D-BC042D

Manufacturer Part Number
CS1D-BC042D
Description
CS1D Dual CPU Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-BC042D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Duplex Unit
Indicator Status when
Power Is Turned ON
52
R
DPL STATUS
L (Active)
R (Non-active) ACTIVE
Duplex Unit indicators
Indicator
ACTIVE
CPU STATUS
ACTIVE
CPU STATUS
CPU STATUS
Green
Green
Red
Note The items set in bold text in the table are the main ones to indicate the status.
Green
(ON)
OFF
Green
(ON)
Green
(flashing)
Red (ON)
Red
(flashing)
OFF
Status
Green (flashing)
Green (ON)
Green (flashing)
OFF
Green (flashing)
Being initialized (transferring
The following table shows the status of Duplex Unit indicators when the power
supply is turned ON. In this example, the left (L) CPU Unit is set as the active
one (ACT.LEFT).
immediately after startup)
data, e.g., user program
The right CPU Unit is active
(ACT).
The right CPU Unit is on
standby (STB).
The right CPU Unit is in
RUN or MONITOR Mode.
The right CPU Unit is being
initialized for duplex opera-
tion, or the CPU is waiting.
Operation
switching
error at the
right CPU
Unit
The right CPU Unit is in
PROGRAM Mode.
Contents
CPU error
Other than
CPU error
Status at startup
Green (ON)
Green (ON)
OFF
OFF
OFF
In PROGRAM
The right CPU Unit is the active (i.e., controlling)
CPU Unit.
Either the right CPU Unit is on standby or the
CPU Unit is stopped.
The right CPU Unit is operating (i.e., in RUN or
MONITOR Mode).
Either the right CPU Unit is being initialized for
duplex operation (transferring or verifying duplex
data) or the CPU is waiting.
While this indicator is flashing, neither of the
CPU Units will begin operation.
Note
1.
2.
A CPU error has occurred at the right CPU Unit.
One of the following operation switching errors
has occurred at the right CPU Unit.
Memory error
Program error
Cycle time overrun error
FALS instruction executed
Fatal Inner Board error (Process-control CPU
Units only)
The right CPU Unit is in PROGRAM Mode, or a
fatal error other than those indicated by a lit or
flashing red indicator has occurred.
Mode
If “Run Under Duplex Initial” in the PLC Set-
up is set to “Start running during initializa-
tion” only the active CPU Unit will start
running during duplex initialization.
This indicator will flash even if a duplex bus
error or a duplex verification error occurs
when the power is turned ON.
Green (ON)
Green (ON)
Green (ON)
OFF
Green (ON)
Duplex Mode
Operating in
Description
OFF
Green (ON)
Green (ON)
OFF
OFF
Simplex Mode
Section 2-3
Operating in