CS1D Duplex System Overview and Features
Automatic Recovery to Duplex Mode
Single CPU Systems
Duplex Power Supply Units
Duplex Communications Units
Duplex Controller Link
Units Using Active/
Standby Units
4
1,2,3...
Note The following Communications Units support duplex operation: The CS1W-
1. There is no need to incorporate special programming for duplex opera-
2. The time required for switching when an error occurs is shortened, en-
With existing Duplex CPU Systems (such as the CVM1D), it is necessary to
manually return the system to Duplex Mode after a CPU Unit error occurs dur-
ing operation in Duplex Mode and operation is switched to Simplex Mode.
With the CS1D Duplex System, operation is automatically returned to the orig-
inal Duplex Mode when the error that caused the switch to Simplex Mode is
cleared.
Unmanned duplex operation can be continued even when incidental errors
occur temporarily due to causes such as noise.
Although only a single CPU Unit is mounted, duplex Power Supply Units,
duplex Communications Units, and online Unit replacement are possible.
Power is always supplied in parallel from two Power Supply Units. Even if one
of the Power Supply Units breaks down, the other one continues providing
power automatically. Power Supply Unit models for AC power and DC power
are both available, and a combination of both types can be used. A Power
Supply Unit that malfunctions or for which a broken line occurs can be con-
firmed by means of flags in the AR Area. If a Power Supply Unit malfunctions,
it can be replaced online without turning OFF the power supply or stopping
operation.
Two Communications Units (see note) are connected by fiber-optic cable. If
one of the Units stops communicating, the other one continues communica-
tions.
CLK12-V1 (H-PCF Cable) and the CS1W-CLK52-V1 (GI Cable) Controller
Link Units.
As shown in the following diagram, two Controller Link Units are mounted in a
single network with identical unit numbers and node addresses. One of the
Controller Link Units is in standby mode.
When an error is detected at the active Controller Link Unit, the standby Con-
troller Link Unit switches to active operating status. This allows communica-
tions to continue without the node being disconnected.
Standby CPU Unit:
Remains on standby while
executing the program.
tions, such as programming to switch when an error occurs, and thus there
is no need for the duplex setup to be considered in individual parameter
settings.
abling operation to be continued without any interruption.
C
P
U
D
P
L
C
P
U
Active CPU Unit:
Controls operation.
No special programming
is required, because
duplex CPU Units are
operating.