60118 SQUARE D, 60118 Datasheet - Page 11

MINIATURE CIRCUIT BREAKER 120V 1A

60118

Manufacturer Part Number
60118
Description
MINIATURE CIRCUIT BREAKER 120V 1A
Manufacturer
SQUARE D
Series
Multi 9r
Datasheet

Specifications of 60118

Actuator Style
Toggle
No. Of Poles
1
Current Rating
1A
Voltage Rating Vac
240V
Mounting Type
DIN Rail
Rohs Compliant
Yes

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
60118-1
Manufacturer:
TE/AMP
Quantity:
30 000
Part Number:
60118-1
Manufacturer:
TE
Quantity:
90 000
Part Number:
60118-1
Manufacturer:
TE
Quantity:
35 000
Part Number:
601181B
Manufacturer:
CDI
Quantity:
339
© 2002–2010 Schneider Electric
All Rights Reserved
Figure 3:
Equipment Enclosure
Electronics
Miscellaneous
Devices
Other
Sensitive
Devices
HACR
Guidelines for Application of UL 489/CSA C22.2 No.5 Circuit Breakers and UL 1077 Supplementary
Protectors
Protected by
Branch
Circuit Breaker
5
UL 489
1
2
UL 1077
UL 1077
Feeder or
Branch
Circuit
NOTE: This is a simplified summary of the standards. Refer to applicable codes for specific applications.
Comparing Terminology for UL 489/CSA C22.2 No.5 and 1077 Standards
The terms used to differentiate these products can cause confusion if a user is not careful. Misapplying
the terms may result in misapplication of the products.
Any one of the following terms can be used to identify supplementary protectors:
Any of the following terms can be used to identify circuit breakers:
Supplementary protector
UL Recognized
UL 1077
The UL symbol
UL 489/CSA C22.2 No.5 Listed Molded Case Circuit Breaker (MCCB)
or Miniature Circuit Breaker (MCB)
UL 489
1
2
3
4
UL 489
UL 489
UL 1077
3
Motor
Control
Internal
Receptacle
Internal
Motor
External
Receptacle
External
Motor
1
2
3
1
2
3
4
5
UL 1077
Applications Permitting Supplementary Protectors
Supplements or provides additional protection for
sensitive electronics inside the equipment.
Used on the load side of branch circuit protection to
protect critical or sensitive internal circuitry such as:
• Computers and microprocessors
• Communications equipment
• Electronic controllers
• Power supplies
• Many other types of equipment
Permitted for protection of motor control circuits
NEC 430-72, unless transformers are in circuit,
then UL 489/CSA C22.2 No.5.
UL 489/CSA C22.2 No.5
Applications Requiring Branch Circuit Protection
Protects conductors entering the OEM equipment.
This required UL 489/CSA C22.2 No.5 device may be
provided integral to the OEM equipment or be
external as part of the distribution system.
May act as branch circuit protection
if it protects the conductor to the utilization equipment.
Required to protect convenience receptacle circuits
(internal or external)
Required to protect an external load circuit leaving
the equipment
Required for motors in the equipment
Required for HACR equipment
(Heating, Air Conditioning, and Refrigeration)
Multi 9™ System Catalog
Section 1—Introduction
07/2010
11