60118 SQUARE D, 60118 Datasheet - Page 19

MINIATURE CIRCUIT BREAKER 120V 1A

60118

Manufacturer Part Number
60118
Description
MINIATURE CIRCUIT BREAKER 120V 1A
Manufacturer
SQUARE D
Series
Multi 9r
Datasheet

Specifications of 60118

Actuator Style
Toggle
No. Of Poles
1
Current Rating
1A
Voltage Rating Vac
240V
Mounting Type
DIN Rail
Rohs Compliant
Yes

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
60118-1
Manufacturer:
TE/AMP
Quantity:
30 000
Part Number:
60118-1
Manufacturer:
TE
Quantity:
90 000
Part Number:
60118-1
Manufacturer:
TE
Quantity:
35 000
Part Number:
601181B
Manufacturer:
CDI
Quantity:
339
© 2002–2010 Schneider Electric
All Rights Reserved
UL 489/CSA C22.2 No. 5 Listed 480Y/277 Vac C60 Circuit Breakers (AC)
The UL 489/CSA C22.2 No.5 Listed 480Y/277 Vac Multi 9 C60 miniature circuit breakers can be used
in 480Y/277 Vac systems. With amperages from 0.5 A to 20 A, they are ideal for fuse replacement, yet
carry the UL 489/CSA C22.2 No.5 Listing that is required for branch circuit applications. See
specifications on Table 2 for dimensions, weights, and interrupting ratings.
Table 7:
Benefits
Standard Features
Interruption Rating
Amperage
Construction
Magnetic Trip Curves
UL 486E Listed Lug
Ring Tongue Screw
Plug-On Auxiliary Modules With
Mechanical Linkage:
Mounting
See selection Table 2 for dimensions, weights, and interrupting ratings.
Satisfies customer’s preferences to use circuit breakers instead of fuses.
Eliminates costs of spare fuses, blown fuse indicators, additional wiring, etc.
Reduces concerns and uncertainty of misapplying a UL 1077 supplementary protector where a
UL 489 branch circuit breaker is required.
Facilitates one common design for UL 489/CSA C22.2 No.5, CSA and IEC applications.
Simplifies installation with a compact, DIN-mounted circuit breaker that accepts a wide range of
accessories.
Offers alternative terminations for ring terminals or cable.
Fast closing: Allows increased withstand to the high inrush currents of some loads.
Trip-free mechanism: Contacts cannot be held in the I-ON position when the circuit breaker is
tripped automatically.
Positive indication of contact disconnect. Green mechanical indication on front face of device
shows that all poles are open.
C curve: Overcurrent protection for all application types. Magnetic release operates from 7 to 10
times ampere rating. (7 to 14 for dc)
D curve: Overcurrent protection for loads with high inrush currents (motors, transformers).
Magnetic release operates between 10 and 14 times ampere rating (no dc rating for D curve).
Suitable for reverse feeding
Allows locking in O-OFF position using padlock attachment.
Specifications for UL 489/CSA C22.2 No.5 Listed 480Y/277 Vac C60 Circuit
Breakers
2P and 3P
1P
0.5 A through 20 A
1P, 2P and 3P
C-curve
D-curve
18–16 AWG (1–1.5 mm
14–10 AWG (2–5 mm
5 mm
MN Undervoltage Trip
MX + OF Shunt Trip/Auxiliary Switch
OF Auxiliary Switch
SD Alarm Switch
35 mm DIN Rail
Section 2—UL and CSA Rated Protection Devices
2
), Cu Only Solid or Stranded Wire
2
), Cu Only Stranded Wire:
Multi 9™ System Catalog
480Y/277 V @ 10kA
277 Vac @ 10kA
7 to 10 Times Ampere Rating
10 to 14 Times Ampere Rating
Torque to 7 lb-in (0.68 N•m)
Torque to 14 lb-in (1.6 N•m)
Torque to 18 lb-in (2 N•m)
07/2010
19

Related parts for 60118