CRT1-ID08TA Omron, CRT1-ID08TA Datasheet - Page 111

no-image

CRT1-ID08TA

Manufacturer Part Number
CRT1-ID08TA
Description
8 In NPN 3 Tier
Manufacturer
Omron
Datasheet

Specifications of CRT1-ID08TA

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
3-5-2
Round Cable I
Power Supply Wiring
Connection Locations for Communications Power Supplies
Note
Master Unit
An OMRON S82-series Power Supply for the communications power supply
for CompoNet Slave Units is recommended.
For details on current consumption for each Unit, refer to Appendix C Current
Consumption Summary.
A 24-VDC power supply is connected individually to each Slave Unit. Power
does not need to be supplied to the Master Unit.
Output current
Insulation
(1) For network power supply Slave Units, the external I/O power supply is
(2) Use a power supply with sufficient capacity considering the inrush current
• Input Bit Slave Units:
• Output Bit Slave Units:
• I/O Bit Slave Units:
Communications power supply current consumption = Bit Slave Unit com-
munications current consumption + (Bit Slave Unit input current × number
of inputs used) + (sensor current consumption × number of sensors used)
Communications power supply current consumption = Bit Slave Unit com-
munications current consumption + (actual load current × number of actu-
ators used)
Communications power supply current consumption = Bit Slave Unit com-
munications current consumption + (Bit Slave Unit input current × number
of inputs used) + (sensor current consumption × number of sensors used)
+ (actual load current × number of actuators used)
Communications
connector
also provided through the Flat Cable from the communications power
supply connected to the Master Unit or the Repeater Unit.
When calculating the output current of the communications power supply,
always include the external I/O current consumption and actual load cur-
rent for network power supply Slave Units.
For example, the power supply current consumption for Bit Slave Unit is
expressed by the following formula.
at startup.
Open Type Connector
Item
Round cable I
Overcurrent
protection (See note.)
(current limit: 4 A)
24-VDC com-
munications
power supply
Use a power supply that equals or exceeds the following total
current consumption:
• The current consumption of all Word Slave Units and
• The current consumption of all Bit Slave Units and the current
Between output and AC power and between output and chas-
sis ground
+
Word Slave Unit
Repeater Units
consumption of their external I/O
Supply communications power directly to each Slave Unit.
Open Type Connector
Note:
When using the UL standards, please install a unit
to restrict current between the external power
supply and this unit to 4 A. (Only communications
power supply)
Word Slave Unit
Specification
Open Type Connector
Word Slave Unit
Section 3-5
Terminating Resistor
Open Type Connector
87

Related parts for CRT1-ID08TA