CRT1-ID08TA Omron, CRT1-ID08TA Datasheet - Page 370

no-image

CRT1-ID08TA

Manufacturer Part Number
CRT1-ID08TA
Description
8 In NPN 3 Tier
Manufacturer
Omron
Datasheet

Specifications of CRT1-ID08TA

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Units with Connectors
Indicator Section
Communications
Indicators
Switch
Setting the Node Address
Output range switch
346
Note
Refer to 4-1-3 Communications Indicators.
The node address is set as a decimal number with the 10s digit set on the left
rotary switch and the 1s digit set on the right rotary switch. (The maximum
node address is 63.)
Rotary switch settings are read when power is turned ON.
(Front side)
(Front side)
(Mounted side)
Pin No.
(1) Always use the default setting (OFF) for pin 7.
(2) Always set pin 8 to ON if the DIP switch is used to set the ranges. If this
(3) The DIP switch settings are read when power is turned ON.
1
2
3
4
5
6
7
8
pin is OFF, the DIP switch settings will not be enabled.
Range settings for output
CH0
Range settings for output
CH1
Always OFF.
Range setting method
Setting
ON
1
4
5
6
7
8
2
3
10s digit of node address
1s digit of node address
See the next table
Default setting: All pins OFF
See the next table
Default setting: All pins OFF
occur if it is set to ON.
ON: Use DIP switch.
Always set this pin to OFF. Malfunctions may
OFF: Use CX-Integrator.
Specification
Section 6-7

Related parts for CRT1-ID08TA