Output Range and
Conversion Data
Summary of the Analog Output Slave Units
Summary of the Analog Output Slave Units
Output Range and Conversion Data
■ Output Range: 0 to 5 V
■ Output Range: 1 to 5 V
The Analog Output Slave Unit converts (DA conversion) digital data (binary
values) stored in the Master Unit into analog signals of 1 to 5 V or 4 to 20 mA
and outputs this.
A summary of the Analog Output Slave Unit is described below.
Digital data that is output is converted to analog data using a set output range
as shown below.
If the output data exceeds the data range for which conversion is possible, the
conversion data saturates at the upper or low limit.
Data of 0000 to 1770 Hex (0 to 6000) is converted to voltage from 0 to 5 V and
output. The output data range for which conversion is possible is from FED4
to 189C Hex (
-0.25 to +5.25 V.
Data of 0000 to 1770 Hex (0 to 6000) is converted to voltage from 1 to 5 V and
output. The output data range for which conversion is possible is from FED4
to 189C Hex (
0.8 to 5.2 V.
8000FED4 (−300)
8000
FED4
(−300)
5.2 V
−0.25 V
5 V
1 V
5.25 V
Voltage
Voltage
0 V
5 V
0 V
0000(0)
300 to +6300) and for this case the output data becomes from
300 to +6300) and for this case the output data becomes from
0.8 V
0000 (0)
(6000)
1770
(6000)
1770
(6300)
189C
(6300)
189C
7FFF
7FFF
Conversion data
Hexadecimal
(decimal)
Conversion data
Hexadecimal
(decimal)
Section 6-3
319