CRT1-ID08TA Omron, CRT1-ID08TA Datasheet - Page 548

no-image

CRT1-ID08TA

Manufacturer Part Number
CRT1-ID08TA
Description
8 In NPN 3 Tier
Manufacturer
Omron
Datasheet

Specifications of CRT1-ID08TA

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Analog I/O Slave Unit (input) Functions
11-4-8 Disconnected Line Detection
Description
11-4-9 User Adjustment
Description
Setting Using the CX-Integrator
524
1,2,3...
8. Click the OK Button and exit the window.
When a disconnection occurs in an analog input line (voltage input or current
input), the Disconnected Line Detection Flag turns ON for each input that is
valid in the number of AD conversion points. The Disconnected Line Detection
Flags are included in the Analog Status Flags.
When Disconnected Line Detection is enabled, the value of AD conversion
data is set to 7FFF hex. When the input returns to a value within the range
that can be converted, the Disconnected Line Detection function will automat-
ically be turned OFF, and normal data conversion will occur.
Disconnected Line detection is supported for input ranges of 1 to 5 V or 4 to
20 mA only. With the 1 to 5 V input range, a disconnected line is detected
when the input voltage is below 0.76 V (less than 6%). With the 4 to 20 mA
input range, a disconnected line is detected when the input current is below
3.04 mA.
Depending on factors such as the characteristics and connection methods of
the input device, the input can be adjusted to compensate for error in the input
voltage or current. The following diagram shows when compensation is
applied to the conversion line at the two points for 0% and 100%.
The following table shows the input ranges that support user adjustment.
1. Turn ON the power supply to the CompoNet Slave Unit.
2. Double-click the icon of the Slave Unit to set in the Network Configuration
–10 to 10 V
4 to 20 mA
0 to 20 mA
0 to 5 V
1 to 5 V
0 to 10 V
0%
Window to open the Configuration Window. (Alternatively, right-click the
icon and select Parameters - Edit from the pop-up menu.)
Input range
Conversion data
–0.25 to 0.25 V
0.8 to 1.2 V
–0.5 to 0.5 V
–11 to –9.0 V
3.2 to 4.8 mA
–1.0 to 1.0 mA
Low Limit
100%
Before adjustment
After adjustment
Voltage/current
4.8 to 5.2 V
4.75 to 5.25 V
9.5 to 10.5 V
9.0 to 11 V
19.2 to 20.8 mA
19 to 21 mA
High Limit
Section 11-4