Analog I/O Slave Unit (output) Functions
11-5-2 User Adjustment
Description
534
7. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
8. Click the OK Button and exit the window.
Depending on factors such as the characteristics and connection methods of
the output device, the output can be adjusted to compensate for error in the
final output. The following diagram shows when compensation is applied to
the conversion line at the two points for 0% and 100%.
The ranges supported for adjustment (–5% to 5%) are shown in the following
table. If adjustment cannot be performed within the following ranges, check
the method being used to connect the output device.
0 to 5 V
1 to 5 V
0 to 10 V
0%
Output range
download the data, and then click the Reset Button to reset the Unit.
Conversion data
–0.25 to 0.25 V
0.8 to 1.2 V
–0.5 to 0.5 V
Low Limit
100%
After adjustment
Before adjustment
Voltage/current
4.8 to 5.2 V
4.75 to 5.25 V
9.5 to 10.5 V
High Limit
Section 11-5