RV4141AM Fairchild Semiconductor, RV4141AM Datasheet - Page 6

CONTROLLER GROUND FAULT 8-SOIC

RV4141AM

Manufacturer Part Number
RV4141AM
Description
CONTROLLER GROUND FAULT 8-SOIC
Manufacturer
Fairchild Semiconductor
Datasheet

Specifications of RV4141AM

Applications
Ground Fault Protection
Current - Supply
10mA
Operating Temperature
-35°C ~ 80°C
Mounting Type
Surface Mount
Package / Case
8-SOIC (3.9mm Width)
Product
Voltage References
Mounting Style
SMD/SMT
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Voltage - Supply
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
RV4141AM
Manufacturer:
FSC
Quantity:
600
Part Number:
RV4141AM
Manufacturer:
FAIRCHILD/仙童
Quantity:
20 000
Part Number:
RV4141AMC1
Manufacturer:
Nanya
Quantity:
25 499
Part Number:
RV4141AMT
Manufacturer:
FAIRCHILD/仙童
Quantity:
20 000
Company:
Part Number:
RV4141AMT
Quantity:
110 000
© 2003 Fairchild Semiconductor Corporation
RV4141A • Rev. 1.0.7
The SCR anode is directly connected to a solenoid or
relay coil. It can be tripped only when its anode is more
positive than its cathode. It must have a high dV/dt
rating to ensure that line noise (generated by electrically
noisy appliances) does not falsely trigger it. Also the
SCR must have a gate drive requirement less than
200μA. C3 is a noise filter that prevents high-frequency
line pulses from triggering the SCR. The relay solenoid
should have a response time of 3ms or less to meet the
UL 943 timing requirement.
Sense Transformers and Cores
The sense and ground/neutral transformer cores are
usually fabricated using high-permeability laminated
steel rings. Their single-turn primary is created by
passing the line and neutral wires through the center of
its core. The secondary is usually from 200 to 1500
turns. Transformers may be obtained from Magnetic
Metals, Inc. (www.magmet.com).
Figure 3. GFI Application Circuit
6
Calculating the Values of R
Determine
requirement. This is typically 5mA in North America
(117V
Determine the minimum delay time required to prevent
nuisance tripping, typically 1 to 2ms. The value of C2
required to provide the desired delay time is:
where:
C2 is in Nf and t is the desired delay time in ms.
The value of R
current specification is:
where:
R
t is the time delay in ms;
P is the period of the line frequency in ms;
I
N is the number of sense transformer secondary turns.
Note:
2.
FAULT
C
R
SET
SET
2
This formula assumes an ideal sense transformer
is used. The calculated value of R
be changed up to 30% when using a non-ideal
transformer.
= 6
is in kΩ;
AC
is the desired ground fault trip current in mA RMS;
=
) and 22mA in the UK and Europe (220V
×
I
t
FAULT
the
SET
×
4.6
COS
to meet the nominal ground fault trip
nominal
×
N
180(t/P)
ground-fault
SET
SET
and C2
may have to
www.fairchildsemi.com
trip-current
AC
(2)
(3)
).