GFL631T-3 INSTRUMENT TRANSFORMER, GFL631T-3 Datasheet - Page 19

GROUND FAULT CURENT

GFL631T-3

Manufacturer Part Number
GFL631T-3
Description
GROUND FAULT CURENT
Manufacturer
INSTRUMENT TRANSFORMER
Datasheet

Specifications of GFL631T-3

Accuracy
15%
Current Measuring Range Ac
30A To 360A
www.GEMultilin.com
in a power system. The output contacts change their normal state only when a phase loss, phase unbalance, phase reversal, under or overvoltage occurs for
longer than the preset trip delay. A total power loss de-energization of the SPVRA relay will not change the output contact position. Recommended for
manually reset switches and breakers applications. The SPVRA is suitable for loss of phase with motor loads.
Three Phase Voltage Monitor
Model SPVRA
STANDARD FEATURES
The Model SPVRA Voltage Sensing Relay is designed to protect against single phase, phase loss, phase unbalance, phase reversal, and under or over voltage
Phase Unbalance: 8 %
Adjustable Trip Delay 1 to 10 seconds after failure occurs.
Output Relay: normally de-energized: Form C contacts for easy circuit conf iguration.
Electro - Mechanical Indicator: retains memory of fault until manually reset .
Door or Panel mounting.
Status Indicator: bi-colored LED
Green: Output Relay De-energized (Normal Condition)
Red: Output Relay Energized (Fault Condition)
Dark: Output relay De-energized (Input Power Off ).
Single Phase, Phase Reversal, Phase Unbalance and Phase Loss Protection: Operates the
output relay after a preselected time.
Overvoltage and Undervoltage Protection: Operates when voltage exceeds 115% or goes
below 80% after a preselected time.
Automatic or Manual -
Automatic Reset to Normal: upon removal of fault conditions.
Manual Reset: Operations from a local pushbutton in cover or from a remote contact .
U L
®
1 4
1 4
7
7
103039, CANADIAN
1 3
1 3
6
6
1 2
1 2
5
5
1 1
1 1
4
4
1 0
1 0
3
3
9
2
2
9
8
1
8
1
C
®
U L
®
103039
APPLICATION:
Protection of three phase electric equipment sensitive to
damage from a phase loss or phase unbalance. Phase
reversal, phase sequence, undervoltage & overvoltage
protection.
NORMAL INPUT VOLTAGES:
120 to 600Vac, 60Hz., 380 to 415Vac, 50Hz.
AMBIENT TEMPERATURE RANGE:
Operation: - 30
Storage - 40
Terminals screws are #6-32 nickel plated brass.
Shipping weight 2.0 lbs.
NUMBER
SPVRA-208
SPVRA-240
SPVRA-480
SPVRA-575
SPVRA-380
SPVRA-415
o
SPVRA-120
C to + 85
MODEL
o
C to +60
10A, 1/3 H.P. AT 120 VAC
10A, 1/2 H.P. AT 240 VAC
AVAILABLE MODELS
3A, 1/2 H.P. AT 600 VAC
CONTACT RATING
o
C.
o
C.
NOMINAL
Vac
120
208
240
480
575
380
415
Hz.
60
60
60
60
60
50
50
13