GFL631T-3 INSTRUMENT TRANSFORMER, GFL631T-3 Datasheet - Page 36

GROUND FAULT CURENT

GFL631T-3

Manufacturer Part Number
GFL631T-3
Description
GROUND FAULT CURENT
Manufacturer
INSTRUMENT TRANSFORMER
Datasheet

Specifications of GFL631T-3

Accuracy
15%
Current Measuring Range Ac
30A To 360A
30
Nominal 120 Volts ac ,or 125 Volts dc is applied between the ’AC ’ and ’ COM ’ term inals. This voltage is half wave rectif ied and applied across the trip capacitor,
giving an output trip voltage. The charge stored in this capacitor (330 uF or 1500 uF) is available between the ‘+’ and ’COM ’ terminals for breaker trip coil
operation. The half wave rectif ication circuitry provides the advantage of maintaining a common neutral connection from input while still maintaining the
charge in the the trip capacitor after control power is lost .
The capacitor is continuously charged when control power is available, providing energy for normal trip coil operation. Because mechanical relays are not
involved, energy for the trip coil operation is immediately available with the loss of control power. When the control power returns, the capacitor automatically
charges to supply energy for the next trip coil.
Capacitor Trip Device
Model CTD
APPLICATION:
Provides a source of energy for circuit
breaker and switch trip coil operation
during a loss of AC control voltage.
NORMAL INPUT:
120 Volts ac,
125 Volts dc.
FREQUENCY:
These devices are protected against inadvertent output short circuit , inductive kickback from the trip coil, and input line voltage surges.
DC to 400Hz.
-
1 & CTD
USA, Canada, Asia, Latin America
Please refer to our website www.GEMultilin.com for more detailed contact information
e-mail: sales.multilin@ge.com
Fax: +1-905-201-2455
Tel: +1-800-547-8629
-
2
Specif ications
Max. Input Voltage:
140 Vac, 125 Vdc surge protected.
Capacitance:
330 uF, CTD-1 + 20% @ 25
1500 uF,CTD-2 + 20% @ 25
Available Energy (
4.72 joules, CTD-1
+ 20% @ 25
21.5 joules, CTD-2
+ 20% @ 25
Normal Output Voltage(
170 Vdc (120 Vac input)
125 Vdc (125 Vac input)
Normal Charge Time (
170 mSec. CTD-1
440 mSec. CTD-2
o
o
C.
C.
**
)
*
)
**
)
INPUT
o
o
C
C
e-mail: gemultilin.euro@ge.com
Europe, Middle East , Africa
* Charge time from full discharge to 90% of max.
** Trip capacitor fully charged to nominal ac input voltage.
Fax: +34-94-485-88-45
Tel: +34-94-485-88-00
capacitor voltage at 25
U L
®
IND. CONT. EQUIP.
Operating Temperature Range:
-30
Storage Temp Range:
-50
Short Circuit Protection:
Continuous
Mounting:
Input Surge Protection:
MOV protected to 65 joules puls e
surge
Vertical or horizontal
o
o
C to 60
C to 80
LISTED
o
o
C
C
o
C.
C
U L
®
FILE NO.
E103039
Electronic Products
OUTPUT

Related parts for GFL631T-3