XTOB004CC1 EATON CUTLER HAMMER, XTOB004CC1 Datasheet - Page 145

Overload Relay

XTOB004CC1

Manufacturer Part Number
XTOB004CC1
Description
Overload Relay
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTOB004CC1

Overload Adjustment Current Min
2.4A
Overload Adjustment Current Max
4A
Coil Voltage Dc Max
220V
Contactor Direction
Non Reversing
Coil Voltage Vdc Nom
220V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
March 2009
Time/Current Curve
Characteristics
The time/current characteristic, the current limiting charac-
teristics and the I
dance with DIN VDE 0660 and IEC 60 947.
The tripping characteristic of the inverse-time delayed over-
load releases (thermal overload releases or “a” releases) for
DC and AC with a frequency of 0 to 400 Hz also apply to the
time/current characteristic.
The characteristics apply to the cold state. At operating
temperature, the tripping times of the thermal releases are
reduced to approximately 25%.
Under normal operating conditions, all three poles of the
device must be loaded. The three main conducting paths
must be connected in series in order to protect single-phase
or DC loads.
With 3-pole loading, the maximum deviation in the tripping
time for 3 times the setting current and upwards is ±20% and
thus in accordance with DIN VDE 0165.
The tripping characteristics for the instantaneous, electro-
magnetic overcurrent releases (short-circuit releases or “n”
releases) are based on the rated current I n , which is also the
maximum value of the setting range for circuit-breakers with
adjustable overload releases. If the current is set to a lower
value, the tripping current of the “n” release is increased by
a corresponding factor.
The characteristics of the electromagnetic overcurrent
releases apply to frequencies of 50/60 Hz. Appropriate
correction factors must be used for lower frequencies up to
16-2/3 Hz, for higher frequencies up to 400 Hz and for DC.
Time/current characteristics, current limiting characteristics
and I
CA08102001E
2
t characteristics are available on request.
2
t characteristics were determined in accor-
For more information visit: www.eaton.com
IEC Contactors & Starters
XT IEC Power Control
Manual Motor Protectors
Figure 34-106. MMP Tripping Characteristics — XTPB, XTPR Frame B
and XTPT (not for XTPM)
Figure 34-107. MMP Tripping Characteristics — XTPR Frame D
200
200
2h
20
10
50
2h
20
10
50
20
10
40
20
20
10
40
20
5
2
1
5
2
1
5
2
5
2
1
5
2
1
5
2
1.5 2
1.5 2
x Rated Operational Current
x Rated Operational Current
3
3
4
4
XTPB, XTPR Frame B
6
6
8 10
8 10
XTPR Frame D
15 20
15 20
XTPT
30
30
34-145