XTOB004CC1 EATON CUTLER HAMMER, XTOB004CC1 Datasheet - Page 300

Overload Relay

XTOB004CC1

Manufacturer Part Number
XTOB004CC1
Description
Overload Relay
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTOB004CC1

Overload Adjustment Current Min
2.4A
Overload Adjustment Current Max
4A
Coil Voltage Dc Max
220V
Contactor Direction
Non Reversing
Coil Voltage Vdc Nom
220V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
34-300
34
Contents
Description
Freedom IEC Combination
Note: For more information, see
CA03801001E.
Product Description
The new Cutler-Hammer
IEC Open Non-reversing and Revers-
ing Combination Motor Controllers
from Eaton’s electrical business
combine a Manual Motor Protector
with an IEC Contactor(s) to provide a
complete motor protection solution by
combining motor disconnect function,
thermal overload protection, mag-
netic short circuit protection and
remote control operation in one com-
pact, assembled unit. These assem-
bled Combination Motor Controllers
cover motors with FLA ratings from
0.11A to 100A.
Application Description
The Freedom IEC Non-reversing
and Reversing Combination Motor
Controllers can be used in the follow-
ing applications:
AE317 Freedom IEC Open Non-reversing
Combination Motor Controller
Motor Controllers
Combination Motor Controller (UL
508, Type F), for Single and Multi
Motor Panels — The IEC
Combination Motor Controllers
combine a Manual Motor Protector
with an IEC Contactor. The A307,
A308, and A309 Manual Motor
Protectors are UL listed as UL 508,
Type E Self-Protected Manual
Combination Starters. This UL
listing allows these devices to be
used in motor circuits without
having to add separate branch short
circuit protection with a Line Side
Adapter. An IEC magnetic contactor
has been added to provide remote
operation of the motor circuit.
Product Selection . . . . . . . . 34-301
Accessories . . . . . . . . . . . . . 34-307
Dimensions . . . . . . . . . . . . . 34-308
IEC Contactors & Starters
Freedom MMPs & Manual and Combination Motor Controllers
Types AM/AE317/357, AE318/358, AE319/359 Freedom IEC Combination Motor Controllers
®
Freedom
Page
For Group Installations or UL 508
Type E/F applications, the A307, A308
and A309 Manual Motor Protectors
have a maximum 600Y/347V rating.
For Group Installations (in-panel
SCPD) applying the traditional 1/3 tap
rule, Freedom Combination Motor
Controllers may be used on 480V Delta
systems. For Group Installations,
applying the more recent 1/10 tap
conductor rule, a maximum 240V Delta
is permitted or 480Y/277V.
For actual UL 508 Type E/F applications
(out-of-panel upstream feeder SCPD
only), the Freedom CMCs may be used
on a maximum 240V Delta or 480Y/
277V system.
For Manual “At Motor” Disconnect
applications, a maximum 240V Delta is
permitted or 480Y/277V and 600Y/347V
slash rated Wye systems.
Features
Table 34-388. Short Circuit Ratings — UL 508
Type E Manual Combination Starter/Motor
Controller
Description
A307
A308
A309
For more information visit: www.eaton.com
See Pages 34-295 – 34-296 for individual
ratings.
Group Motor Installations — Since
the Manual Motor Protectors (Man-
ual Combination Starters) are UL
listed for Group Motor Installations,
the IEC Combination Motor Control-
lers provide a compact, assembled
package for Group Motor Installa-
tions up to 480V.
ON/OFF rotary handle with lockout
provision
Visible trip indication
Test trip function
Motor applications from 0.11A to
100A
Class 10 overload protection
Built-in heater and magnetic trip
elements to protect the motor
Phase loss sensitivity
Type 2 coordination
Ambient compensated up to
140°F (60° C)
High Fault Short Circuit Ratings:
Magnet coil terminals located at
bottom of Contactor for easy access
and wiring
65 kA at 480V for AE317/357,
AM317/357 and AE318/358 motor
controllers
50 kA at 480V for AE319/359
motor controllers
Specification
65 kA @ 240V, 480Y/277V
30 kA @ 600Y/347V up to 12.5A
65 kA @ 240V, 480Y/277V
25 kA @ 600Y/347V
65 kA @ 240V, 480Y/277V
30 kA @ 600Y/347V up to 75A
Standards and Certifications
Instructional Leaflets
IL49490
IL49491
IL49492
Pub50278
Pub50279
Pub50280
Pub50281
Pub50342
Pub50343
Pub50417
Pub50545
AP03402001E Application Note
AC and DC coils offered in a variety
of voltages
1NO and 1NC auxiliary contacts
front mounted on MMP —
standard on all combination
motor controllers
1NO auxiliary contact — standard
on all magnetic contactors
DIN rail or panel mount —
AE317, AM317 and AM357 motor
controllers
Mounting plates — standard on
AE318, AE319, AE358 and AE359
motor controllers
Adjustment dial for setting motor FLA
Short circuit trip at 13 times the
maximum setting of the FLA
adjustment dial
IEC Type 2 Approved per
IEC 60947-4-1
UL Listed File No. E218618
CE Mark
A307 Manual Motor
Protector
A308 Manual Motor
Protector
A309 Manual Motor
Protector
Non-reversing AM317,
AE317 & AE318
Combination Motor
Controller, AC Coils
Reversing AE357 &
AE358 Combination
Motor Controllers, AC
Coils
Reversing AM357
Combination Motor
Controllers,
AC & DC Coils
Non-reversing AM317,
AE317, & AE318
Combination Motor
Controllers, DC Coils
Non-reversing AE319
Combination Motor
Controllers, AC & DC
Coils
Reversing AE359
Combination Motor
Controllers, AC & DC
Coils
Reversing AE357 &
AE358 Combination
Motor Controllers, DC
Coils
Wire Connector Link
Installation
CA08102001E
March 2009

Related parts for XTOB004CC1