XTOB004CC1 EATON CUTLER HAMMER, XTOB004CC1 Datasheet - Page 273

Overload Relay

XTOB004CC1

Manufacturer Part Number
XTOB004CC1
Description
Overload Relay
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTOB004CC1

Overload Adjustment Current Min
2.4A
Overload Adjustment Current Max
4A
Coil Voltage Dc Max
220V
Contactor Direction
Non Reversing
Coil Voltage Vdc Nom
220V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
March 2009
Contents
Description
Product Family Overview
Interchangeable Heater
Accessories . . . . . . . . . . . . . . . 34-277
Renewal Parts . . . . . . . . . . . . . 34-284
Note: For more information, see
CA03402001E.
Product Description
C306 Overload Relays are designed for
use with CE or CN non-reversing and
reversing contactors. Four sizes are
available for overload protection up to
144 amperes.
CA08102001E
Overload Relays
Product Description . . . . . . 34-261
Features . . . . . . . . . . . . . . . 34-261
Standards and
Product Description . . . . . . 34-273
Features . . . . . . . . . . . . . . . 34-273
Standards and
Factory Modifications . . . . 34-273
Accessories. . . . . . . . . . . . . 34-273
Replacement Parts . . . . . . . 34-274
Product Selection . . . . . . . 34-275
Heater Pack Selection . . . . 34-275
Auxiliary Contacts . . . . . . . 34-277
DC Magnet Coils . . . . . . . . 34-279
Certifications . . . . . . . . . . 34-261
Certifications . . . . . . . . . . 34-273
32 Ampere Overload
Cat. No. C306DN3B
Page
Features
Factory Modifications
Table 34-339. C306 Thermal Overload Relays with Mounting Adapter
Accessories
Table 34-340. DIN Rail and Panel Mounting Adapter
Consists of a thermal overload relay mounted to a terminal base adapter — permits fast and easy
installation.
Description
C306DN3B + C306TB1
C306GN3B + C306TB2B
These adapters are required when component overload relays are to be separately mounted. The
terminal base adapter includes line terminals and connects with the overload relays listed in
Table 34-339.
Description
For 32 Ampere Overload Relay
For 75 Ampere Overload Relay
For more information visit: www.eaton.com
This Series “B” adapter will accept Series “A” or “B” overload relays (C306GN3 or C306GN3B).
C306TB2 can only be used with C306GN3.
Selectable manual or automatic
reset operation.
Interchangeable heater packs
adjustable ±24% to match motor
FLA and calibrated for use with
1.0 and 1.15 service factor motors.
Class 10 or 20 heater packs.
Load lugs built into relay base.
Bimetallic, ambient compensated
operated. Trip free mechanism.
Cat. No. C306TB1
IEC Contactors & Starters
Freedom
Relays — Interchangeable Heater Overload
Heater packs for 32 ampere over-
load relay will mount in 75 ampere
overload relay — useful in derat-
ing applications such as jogging.
Standards and Certifications
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C
Catalog
Number
C306DT3B
C306GT3B
Catalog
Number
C306TB1
C306TB2B
Electrically isolated NO-NC contacts
(pull RESET button to test).
Overload trip indication.
Shrouded or “fingerproof”
terminals to reduce possibility of
electrical shock.
Meets UL508 single-phasing
requirements.
UL listed
CSA certified
NEMA compliance and EN60947-4-1
IEC 947-4-1 and (CE) Mark
Price
U.S. $
Price
U.S. $
34-273
34