Basic Procedures
142
1,2,3...
Note The I/O tables, user program, and PLC Setup data in CS1D CPU Units is
backed up in the built-in flash memory. The BKUP indicator will light on the
front of the CPU Unit when the backup operation is in progress. Do not turn
OFF the power supply to the CPU Unit when the BKUP indicator is lit. The
data will not be backed up if power is turned OFF.
Using the CX-Programmer Online
Use the following procedure to register the I/O tables with the CX-Program-
mer connected to the CPU Unit and all of the Units mounted to the system.
1. Set the device type in the CX-Programmer as shown in the following table.
2. Place the CX-Programmer online to the PLC.
3. Create the I/O tables.
4. With a Duplex CPU System, confirm that the DPL STATUS indicator on the
Using the CX-Programmer Offline
Use the following procedure to create the I/O tables offline with the CX-Pro-
grammer and later transfer the I/O tables to the CPU Unit.
a) With the CPU Unit in PROGRAM mode, double-click IO Table on the
b) Select Options and then Create. The models and positions of Units
Note With a Duplex CPU System, the I/O tables cannot be created di-
Duplex Unit flashes green after the I/O tables have been created in the ac-
tive CPU Unit. This indicates that the duplex system is being initialized,
e.g., the I/O tables that were written to the active CPU Unit are also being
written to the standby CPU Unit.
Note If an inconsistency is detected between the two CS1D CPU Units,
Duplex CPU Systems
Single CPU Systems
project tree in the main window. The I/O Table Window will be dis-
played.
mounted to the Racks will be written to the registered I/O tables in the
CPU Unit. With a Duplex CPU System running in Duplex Mode, the
I/O tables will automatically be created in both the active and standby
CPU Units.
Status of actually
mounted Units
rectly in the standby CPU Unit.
a duplex verification error will occur and the DPL STATUS indica-
tor will flash red. If this happens, press the initialization switch. Un-
less there is a hardware error causing the inconsistency, the error
should be cleared.
System
SYSMAC
CS1D-CPU67H
PROGRAMMABLE CONTROLLER
MCPWR
PORT
ERR/ALM
PRPHL
RUN
INH
BUSY
BKUP
COMM
DUPLEX
DUPLEX
RIGHT CPU
INIT.
LEFT CPU
DPL SW
ON
ON
SW
Active
CPU Unit
SYSMAC
CS1D-CPU67H
PROGRAMMABLE CONTROLLER
MCPWR
PORT
ERR/ALM
PRPHL
RUN
INH
BUSY
BKUP
COMM
CS1H-H
Not supported
When the I/O tables are
created, they are placed
in the active CPU Unit.
CX-Programmer
version 3.@
Create I/O Table
operation performed.
CX-Programmer
or
CS1H-H or CS1D-H
CS1D-S
version 4 or higher
CX-Programmer
Programming
Console
RUN
PR
PRO27
PR
PROGRAMMING CONSOLE
MONITOR
FUN
AND
E
B
A
OGRAMMING CONSOLE
LD
7
4
1
O27
0
EAR MIC
PROGRAM
SFT
OR
OUT
F
C
8
5
2
NOT
CNT
TIM
D
9
6
3
TR
DM
EXT
LR
CH
Section 4-2
HR
(Peripheral
port only)

Related parts for CS1D-IC102D