CS1D-IC102D Omron, CS1D-IC102D Datasheet - Page 220

no-image

CS1D-IC102D

Manufacturer Part Number
CS1D-IC102D
Description
CS1D Dual IO Control Unit
Manufacturer
Omron
Datasheet

Specifications of CS1D-IC102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Output Surge Current
5-4-5
I/O Signal Wiring
Inductive Loads
Wiring Methods
Reducing Electrical Noise
Use the following formula to determine the resistance and rating for the
bleeder resistor.
When connecting a transistor or triac output to an output device having a high
surge current (such as an incandescent lamp), steps must be taken to avoid
damage to the transistor or triac. Use either of the following methods to
reduce the surge current.
Method 1
Add a resistor that draws about 1/3 of the current consumed by the bulb.
Method 2
Add a control resistor as shown in the following diagram.
Whenever possible, place I/O signal lines and power lines in separate ducts or
raceways both inside and outside of the control panel.
If the I/O wiring and power wiring must be routed in the same duct, use
shielded cable and connect the shield to the GR terminal to reduce noise.
When an inductive load is connected to an I/O Unit, connect a surge suppres-
sor or diode in parallel with the load as shown below.
R
Suspended duct
V
I
SYSMAC
SYSMAC
ON
1
2
OUT
COM
OUT
COM
V
I: Leakage current (mA)
R: Bleeder resistance (K )
ON
: ON voltage of the load (V)
R
R
L
L
1
In-floor duct
+
2
+
1 = I/O cables
2 = Power cables
1
Conduits
Section 5-4
2
185