XTOB001CC1 EATON CUTLER HAMMER, XTOB001CC1 Datasheet - Page 113

Overload Relay

XTOB001CC1

Manufacturer Part Number
XTOB001CC1
Description
Overload Relay
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTOB001CC1

Overload Adjustment Current Min
0.6A
Overload Adjustment Current Max
1A
Coil Voltage Dc Max
220V
Contactor Direction
Non Reversing
Coil Voltage Vdc Nom
220V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
March 2009
Contents
Description
Overload Relays — C396
Catalog Number
Product Selection . . . . . . . . . . 34-114
Accessories . . . . . . . . . . . . . . . 34-115
Technical Data and
Dimensions . . . . . . . . . . . . . . . 34-117
Reference Data . . . . . . . . . . . . 34-210
Catalog Number Selection
Table 34-137. C396 Electronic Overload Relays — Catalog Numbering System
CA08102001E
Selection . . . . . . . . . . . . . . . . 34-113
Specifications . . . . . . . . . . . . 34-116
C396 = C396 Electronic Overload Relay
C396 Electronic
Overload Relay
Device Type
2 = Standard
Feature Set
A = 45 mm
B = 65 mm
C = 110 mm
Frame Size
Page
A = Auto
Reset Type
C 3 9 6 A 2 A P 0 5 S E L A X
Product Description
The C396 is a self-powered, robust
electronic overload designed for inte-
grated use with Freedom NEMA,
IEC, and DP contactors. The overload
can be ordered as a stand-alone
version that is designed for Panel-
Mounting and for use on 35 mm DIN
rail. The C396 has an FLA range of
0.1 – 150 Amps with internal CTs, and
up to 1500 Amps using external CTs.
Features
For more information visit: www.eaton.com
Standard Version: Selectable trip
class (5, 10, 20, 30) with Selectable
Manual or Auto Reset
Broad 5:1 FLA range
Self-Powered Design, will accept AC
voltages from 12 – 690V 50/60 Hz
Ambient Temperature
Compensation
Low Heat Generation
Phase Loss Protection
Phase Unbalance Protection
Electrically isolated 1NO-1NC
Contacts (Push-to-Test)
Trip Status Indicator
FLA range of 0.1 – 1500 Amps
IEC Contactors & Starters
XT IEC Power Control
Overload Relays — C396
Frame A (45 mm)
P05 = 0.1 – 0.5
002 = 0.4 – 2.0
005 = 1 – 5
008 = 1.6 – 8
032 = 6.4 – 32
045 = 9 – 45
Frame B (65 mm)
075 = 15 – 75
110 = 22 – 110
Frame C (110 mm)
150 = 30 – 150
Max. Amperes
Current Rating
AX = All Frame Sizes
Frame B
Frame C
SEL = Selectable
XB = 0.1 – 0.5A
XC = 0.1 – 0.5A
Standards and Certifications
0.4 – 2.0A
1 – 5A
1.6 – 8A
6.4 – 32A
0.4 – 2.0A
1 – 5A
1.6 – 8A
6.4 – 32A
Stand-Alone Overload Relay Suffix
UL Listed Components: Stand-
alone, starter-mounted devices and
remote reset kit.
CSA Certified Components: Stand-
alone, starter-mounted devices and
remote reset kit.
IEC EN 60947-4-1, EN 60947-5-1
CE
RoHS
Class
XT IEC Adapter Suffix
Frame D
Frame F – G
XD =
XF = 22 – 110A
15 – 75A
6.4 – 32A
9 – 45A
34-113
34

Related parts for XTOB001CC1