XTOB001CC1 EATON CUTLER HAMMER, XTOB001CC1 Datasheet - Page 307

Overload Relay

XTOB001CC1

Manufacturer Part Number
XTOB001CC1
Description
Overload Relay
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTOB001CC1

Overload Adjustment Current Min
0.6A
Overload Adjustment Current Max
1A
Coil Voltage Dc Max
220V
Contactor Direction
Non Reversing
Coil Voltage Vdc Nom
220V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
March 2009
Accessories
Table 34-403. Line Side Adapters (C320LSA1 and C320LSA2) —
When to Use Them for U.S. Applications
Reference: Technical Paper AP03402001E.
Note: Line Side Adapters are not required for non-U.S. applications. Most countries outside
of the U.S. classify the MMP as a thermal magnetic circuit breaker.
Table 34-404. Accessories
CA08102001E
SCPD = Short Circuit Protective Device (Circuit Breaker, Fuses).
MMP = Manual Motor Protector.
A308 MMP does not require a Line Side Adapter.
Not Required
Using the in-panel
Main SCPD
Group Installation
Line Side Adapter
Types AM/AE317/357 & AE319/359
Freedom Combination Motor Controller (CMC)
Motor Controllers
IEC Combination
UL 508 Type F Combination
Motor Controller — Only
Upstream Feeder SCPD
required; no dedicated
in-panel Main SCPD for
MMP /Contactor
Description
Line Side Adapter for A307 MMPs
(Required for use with A307 MMPs
only when used as Self-Protected
Manual Combination Starters. Not
required for Group Installation.)
Line Side Adapter for A309 MMPs
(Required for use with A309 MMPs
only when used as Self-Protected
Manual Combination Starters. Not
required for Group Installation.).
Wiring Connector Link
(Electrical and mechanical intercon-
nection between A307 MMP + CE12
Freedom Miniature FVNR/FVR
Contactor)
Wiring Connector Link
(Electrical and mechanical intercon-
nection between A307 MMP + CE15
Freedom 45 mm IEC FVNR Contactor
— Sizes A – F)
Wiring Connector Link
(Electrical and mechanical intercon-
nection between A308 MMP + CE15
Freedom 65 mm IEC FVNR Contactor
— Sizes G – K)
Required
Line Side Adapter
MMP /Contactor
For more information visit: www.eaton.com
IEC Contactors & Starters
Freedom MMPs & Manual and Combination Motor Controllers
Types AM/AE317/357, AE318/358, AE319/359 Freedom IEC Combination Motor Controllers
Not required for any application
Types AE318/358
UL 508 Type E Self-protected
Manual Combination Starter —
Only Upstream Feeder SCPD
required; no dedicated in-panel
Main SCPD for MMP
Motor Controllers
IEC Combination
Line Side Adapter
Catalog
Number
C320LSA1
C320LSA2
C320WC25
C320WC45
C320WC65
MMP
Only
Price
U.S. $
Protection in Different Controller
Types
A UL 508 Type E Self-protected Manual
Combination Starter/Motor Controller
consists of a single device having inte-
gral short circuit protection, a main set
of contacts, motor overload protec-
tion, and may also include a UL Listed
Line Side Adapter (see Table 34-403).
This type of controller is a legitimate
short-circuit circuit protective device
and disconnect means for the down-
stream motor. It does require an
upstream feeder short circuit protec-
tive device, but does not require a ded-
icated branch circuit protection or a
disconnect means. A UL 508 Type E
rating means that the unit clears a fault
and does not experience any welding
of the power poles. A UL 508 Type E
self-protected manual motor controller
will remain fully functional should a
short circuit within its ratings occur.
E.g. A307, A308 and A309.
A UL 508 Type F Combination Motor
Controller consists of a UL Listed
Type E Self-protected Manual Combi-
nation Starter/Motor Controller, a UL
Listed Contactor, and possibly a UL
Listed Line Side Adapter (see Table 34-
403). While the UL 508 Type E self-
protected manual motor controller
of this combination motor controller
device is a legitimate short circuit
protective device and disconnect
means for the downstream motor,
the contactor is not “self-protected.”
E.g. AM317 – AE319 and AM357 –
AE359.
In addition, as a complete assembly or
with modular components, the device
may have Type 2 Coordination certifi-
cation. Type 2 Coordination means the
Starter or Controller must exhibit little
or no damage following a major short
circuit fault and should be able to be
returned to proper service without
replacing any parts. E.g. All Freedom
CMCs and MMPs.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD1
34-307
34