XTOB001CC1 EATON CUTLER HAMMER, XTOB001CC1 Datasheet - Page 210

Overload Relay

XTOB001CC1

Manufacturer Part Number
XTOB001CC1
Description
Overload Relay
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTOB001CC1

Overload Adjustment Current Min
0.6A
Overload Adjustment Current Max
1A
Coil Voltage Dc Max
220V
Contactor Direction
Non Reversing
Coil Voltage Vdc Nom
220V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
34-210
34
Type 2 Coordination
What is it?
The International Electrotechnical
Commission (IEC) developed short
circuit performance criteria for
contactors and starters called Type 1
coordination and Type 2 coordination.
This defines motor controller protec-
tion levels following a short circuit
fault. In order to achieve this perfor-
mance, the combination of a motor
controller (contactor or starter) and
short circuit protective device (manual
motor protector, circuit breaker or
fuse) must meet the following criteria
as specified by IEC 60947-4-1 — Low
Table 34-249. 400, 415V Type 2 Coordination — MMC
Note: See Page 34-216 for more information on Wye-Delta (Star Delta) applications.
P
(kW)
11.0
15.0
11.0
15.0
18.5
22.0
30.0
34.0
0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.10
1.50
2.20
3.00
4.00
5.50
7.50
5.50
7.50
Values in parentheses ( ) are for Type 1 Coordination.
Underscore (_) indicates magnet coil suffix required. See Table 34-261, Page 34-216.
IEC Contactors & Starters
XT IEC Power Control
Reference Data
I e
(A)
11.3
16.0
21.7
29.3
11.3
16.0
21.7
29.3
36.0
41.0
55.0
63.0
0.31
0.41
0.60
0.80
1.10
1.50
1.90
2.60
3.60
5.00
6.60
8.50
0.21
I q
(kA)
50 (150)
50 (150)
50 (150)
50 (150)
50 (150)
50 (150)
50 (150)
50 (150)
50 (150)
50 (150)
50 (150)
50 (150)
50 (150)
50
50
50
50
50
50
50
50
50
50
50
50
voltage switchgear and controlgear —
Part 4-1: Contactors and motor-starters
— Electromechanical contactors and
motor-starters:
Type 1 Coordination requires that
under short circuit conditions, the con-
tactor or starter shall cause no danger
to persons or installation and may not
be suitable for further service without
repair and replacement of parts.
In this case, significant damage is
allowed to the contactor/starter (e.g.
contact welding, burning, or disinte-
gration) and the overload relay (e.g.
component harm or heater element
burn-out).
For more information visit: www.eaton.com
MMP
Catalog Number
XTPRP25BC1
XTPRP40BC1
XTPRP63BC1
XTPRP63BC1
XTPR001BC1
XTPR1P6BC1
XTPR1P6BC1
XTPR2P5BC1
XTPR004BC1
XTPR004BC1
XTPR6P3BC1
XTPR010BC1
XTPR010BC1
XTPR012BC1
XTPR016BC1
XTPR025BC1
XTPR032BC1
XTPR016DC1
XTPR016DC1
XTPR025DC1
XTPR032DC1
XTPR040DC1
XTPR050DC1
XTPR058DC1
XTPR063DC1
Contactor
Catalog Number
XTCE007B10_
XTCE007B10_
XTCE007B10_
XTCE007B10_
XTCE007B10_
XTCE007B10_
XTCE007B10_
XTCE007B10_
XTCE007B10_
XTCE007B10_
XTCE007B10_
XTCE018C10_
XTCE018C10_
XTCE018C10_
XTCE018C10_
XTCE025C10_
XTCE032C10_
XTCE018C10_
XTCE018C10_
XTCE025C10_
XTCE032C10_
XTCE040D00_
XTCE050D00_
XTCE065D00_
XTCE065D00_
Type 2 Coordination requires that
under short circuit conditions, the con-
tactor or starter shall cause no danger
to persons or installation and shall be
suitable for further use. The risk of
contact welding is recognized, in which
case the manufacturer shall indicate
the measures to be taken as regards to
the maintenance of the equipment.
In this case, the contactor/starter is
able to continue use after the occur-
rence of a short circuit fault. Light
contact burning or tack welding may
occur provided the contacts are easily
separable.
MMC
Catalog Number
XTSCP25BB_
XTSCP40BB_
XTSCP63BB_
XTSCP63BB_
XTSC001BB_
XTSC1P6BB_
XTSC1P6BB_
XTSC2P5BB_
XTSC004BB_
XTSC004BB_
XTSC6P3BB_
XTSC010BC_
XTSC010BC_
XTSC012BC_
XTSC016BC_
XTSC025BC_
XTSC032BC_
XTSC016DC_
XTSC016DC_
XTSC025DC_
XTSC032DC_
XTSC040DD_
XTSC050DD_
XTSC058DD_
XTSC063DD_
CA08102001E