XTOB001CC1 EATON CUTLER HAMMER, XTOB001CC1 Datasheet - Page 259

Overload Relay

XTOB001CC1

Manufacturer Part Number
XTOB001CC1
Description
Overload Relay
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTOB001CC1

Overload Adjustment Current Min
0.6A
Overload Adjustment Current Max
1A
Coil Voltage Dc Max
220V
Contactor Direction
Non Reversing
Coil Voltage Vdc Nom
220V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
March 2009
Auxiliary Contacts Front and Side Mounted
A total of six auxiliary contacts are available to be used with
the mini control line.
Front mounted auxiliary contacts are available in three
contact configurations (1NO-1NC, 2NO and 2NC) and can be
screw mounted to non-reversing and reversing contactors
with screw pressure plate terminals only.
Side mounted auxiliary contacts are available for the
miniature control product line in three terminal versions:
screw pressure plate, quick connect and solder pin. The
side mounted auxiliary is mounted to the left side of non-
reversing contactors without tools. Only one side mounted
auxiliary can be mounted on these products.
Table 34-318. Front Mount Auxiliary Contacts for Screw Pressure Plate
Terminals — Only Mini Contactor and Control Relay
Table 34-319. Side Mount Auxiliary Contacts for Screw Pressure Plate,
Quick Connect, Solder Pin Terminals and Control Relays
Application Notes
CA08102001E
Add-On Auxiliary
Contacts Configuration
1NO-1NC
2NO
2NC
Terminal Type
Contactor/Control Relay
Screw Pressure Plate
Quick Connect
Solder Pin
Side mounted auxiliary contacts can not be used simulta-
neously with front mounted auxiliary contacts.
Auxiliary contacts can not be used with low power DC Coil
Suffix designations T2, T3, V2 or V3.
Side mounted auxiliary contacts can not be used with
mechanically interlocked contactors.
Auxiliary contacts used with devices having screw pres-
sure plate terminals are UL Listed and side mounted
auxiliary contacts used with devices having quick connect
or solder pin terminals are UL Recognized.
Add-On
Auxiliary
Contacts
Configuration
1NO-1NC
1NO-1NC
1NO-1NC
Catalog
Number
C320MCF11
C320MCF20
C320MCF02
Catalog
Number
C320MCS11
C320MBS11
C320MPS11
For more information visit: www.eaton.com
IEC Contactors & Starters
Freedom Miniature Controls
Accessories
Price
U.S. $
Price
U.S. $
Overload Relays
Table 34-320. Bimetallic Overload Relay — Class 10
Note: Overload relays to be used with Pressure Plate Terminal type
Mini Contactors only.
Thermal Overload Relay C312 — Technical Data
Conformity to Standards
Thermal (Bimetallic) Overload Relay, C312 OL Relay
Motor FLA
in Amperes
1.00 – 1.60
1.60 – 2.40
2.40 – 4.0
4.0 – 6.0
6.0 – 9.0
9.0 – 12.0
.10 –
.16 –
.24 –
.40 –
.60 – 1.00
IEC 947-4-1, 947-5-1, CE
UL 508, CSA 22.2
Insulation Voltage (U i ): 690V AC
Rated Operational Voltage (U e ): 690V AC
Ambient Temperature: -13° to 122°F (-25° to +50°C)
temperature compensated
Storage: -40° to 158°F (-40° to +70°C)
Impulse Withstand Voltage (U imp ): 6 kV
Climatic Resistance —
Mounting Position: ± 30 from vertical position, not
horizontal, not upside down, 5 mm side by side
mounting distance
Switching Frequency with Avoidance of Nuisance
Trippings — max. ops./h: 15
≤ 40% ED — max. ops./h: 60 (if 6X in startup time ≤1 s)
Overvoltage Category/Pollution Degree: III/3
Safe Isolation to IEC 536: 300V AC
Conventional Free Air Thermal Current (I th ): 6.0A
Acc. to DIN 50 017
Acc. to UTE C 63 – 100: IEC 68-2-3, IEC 68-2-30
.16
.24
.40
.60
Max. Fuse —
Type gL A
10.0
10.0
10.0
20.0
1.0
2.0
2.0
4.0
6.0
6.0
.5
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 1CD7
Overload Relay
Wt.
Lbs. (kg)
.154 (.070)
.154 (.070)
.154 (.070)
.154 (.070)
.154 (.070)
.154 (.070)
.154 (.070)
.154 (.070)
.154 (.070)
.154 (.070)
.154 (.070)
Catalog
Number
C312AN3A
C312AN3B
C312AN3C
C312AN3D
C312AN3E
C312AN3F
C312AN3G
C312AN3H
C312AN3J
C312AN3K
C312AN3L
Price
U.S. $
34-259
34