PAXS0010 Red Lion Controls, PAXS0010 Datasheet - Page 25

Strain Gauge Meter

PAXS0010

Manufacturer Part Number
PAXS0010
Description
Strain Gauge Meter
Manufacturer
Red Lion Controls
Type
Strain Gager
Datasheets

Specifications of PAXS0010

No. Of Digits / Alpha
5
Meter Function
DC Millivoltmeter
Meter Range
± 24mV To ± 240mV
Digit Height
14.2mm
Power Consumption
11W
Operating Temperature Range
0°C To +50°C
Supply Voltage Dc, Min
11V
Accuracy
0.07% of Reading +4 µV
Brand/series
PAX
Character Height
0.56 in.
Connection Type
2-Wire (Single-Ended), 4-Wire Bridge (Differential)
Cut Out, Panel
1⁄8 DIN
Dimensions
4.2" L × 3.8" W × 1.95" H
Display Digit Height
0.56 "
Display Resolution
1 μV/10 μV
Display Type
LED
Function
Strain Gage
Input Type
Strain Gauge/Bridge Input
Number Of Digits
5
Primary Type
Electronic
Range, Measurement
±24/±240 mvDC
Special Features
Programmable Function Keys
Temperature Range
0 to +50 °C
Temperature, Storage
–40 to +60 °C
Termination
Cage Clamp
Voltage, Input
11-36 VDV, 24 VAC
Lead Free Status / RoHS Status
na
TROUBLESHOOTING
PARAMETER VALUE CHART
PAX MODEL NUMBER
* Decimal point location is model and programming dependent.
DISPLAY
1-INP
rAN6E
tyPE
SCALE
COUPL
dECPt
round
OFFSt
FILtr
bANd
ICE
PtS
StYLE
INP 1
dSP 1
INP 2
dSP 2
INP 3
dSP 3
INP 4
dSP 4
INP 5
dSP 5
PROBLEM
NO DISPLAY
PROGRAM LOCKED-OUT
MAX, MIN, TOT LOCKED-OUT
INCORRECT INPUT DISPLAY VALUE
“OLOL” in DISPLAY (SIGNAL HIGH)
“ULUL” in DISPLAY (SIGNAL LOW)
JITTERY DISPLAY
MODULES or PARAMETERS NOT ACCESSIBLE
ERROR CODE (Err 1-4)
DISPLAY ZERO’S AT LEVELS BELOW 1% OF RANGE
Signal Input Parameters
PARAMETER
MODEL DEPENDENT
PAXT: INPUT TYPE
PAXT: TEMPERATURE SCALE
PAXH: INPUT COUPLE
* DISPLAY RESOLUTION
DISPLAY ROUNDING INCREMENT
PAXT: DISPLAY OFFSET
FILTER SETTING
FILTER ENABLE BAND - PAXH
PAXT: ICE POINT SLOPE
SCALING POINTS
SCALING STYLE - NOT PAXT
* INPUT VALUE 1
* DISPLAY VALUE 1
* INPUT VALUE 2
* DISPLAY VALUE 2
* INPUT VALUE 3
* DISPLAY VALUE 3
* INPUT VALUE 4
* DISPLAY VALUE 4
* INPUT VALUE 5
* DISPLAY VALUE 5
For further assistance, contact technical support at the appropriate company numbers listed.
-
PAXH
0. 0 20
0. 5
________ Meter# _____________ Security Code __________
FACTORY
SETTING
tc-.
0. 0 00
1. 0 00
1000
0. 0 00
0. 0 00
0. 0 00
0. 0 0
KEY
°F
AC
1. 0
10
0
1
0
2
0
0
0
0
REMEDIES
CHECK: Power level, power connections
CHECK: Active (lock-out) user input
ENTER: Security code requested
CHECK: Module 3 programming
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level,
PERFORM: Module 9 Calibration (If the above does not correct the problem.)
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level
INCREASE: Module 1 filtering, rounding, input range
CHECK: Wiring is per EMC installation guidelines
CHECK: Corresponding plug-in card installation
PRESS: Reset KEY (If cannot clear contact factory.)
PROGRAM: Module 4 as Hi-t: 0.0 LO-t: 3271.1 (to disable zero chop feature)
USER SETTING
Programmer ________________ Date ________
Module 4 Display Offset is zero, press DSP for Input Display
25
DISPLAY
INP 6
dSP 6
INP 7
dSP 7
INP 8
dSP 8
INP 9
dSP 9
INP 10
dSP 10
INP 11
dSP 11
INP 12
dSP 12
INP 13
dSP 13
INP 14
dSP 14
INP 15
dSP 15
INP 16
dSP 16
PARAMETER
* INPUT VALUE 6
* DISPLAY VALUE 6
* INPUT VALUE 7
* DISPLAY VALUE 7
* INPUT VALUE 8
* DISPLAY VALUE 8
* INPUT VALUE 9
* DISPLAY VALUE 9
* INPUT VALUE 10
* DISPLAY VALUE 10
* INPUT VALUE 11
* DISPLAY VALUE 11
* INPUT VALUE 12
* DISPLAY VALUE 12
* INPUT VALUE 13
* DISPLAY VALUE 13
* INPUT VALUE 14
* DISPLAY VALUE 14
* INPUT VALUE 15
* DISPLAY VALUE 15
* INPUT VALUE 16
* DISPLAY VALUE 16
FACTORY
SETTING
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0
0
0
0
0
0
0
0
0
0
0
USER SETTING

Related parts for PAXS0010