Setting up the PROFINET IO network
3-4-5
Establishing the PROFINET IO network
Note
This section describes how to create, connect and configure the PROFINET
IO network using the CX-ConfiguratorFDT software and the Device DTMs.
1 Select the Network Components (see previous section) and build the
2 Connect the Personal Computer to the Ethernet network. Note that the
3 Start the CX-ConfiguratorFDT software and install the appropriate GSDML
4 Scan the PROFINET network with the PROFINET Scan View included in
5 Add the PROFINET IO Controller as parent in the Network View. Configure
6 Build up the network within CX-ConfiguratorFDT. Add the IO Devices to the
7 Allocate the modules of the IO Devices to the intended PLC memory areas.
8 Download the configuration to the IO Controller.
9 Confirm proper operation by checking the Monitoring GUI of DTM and LED
A common mistake when implementing IO Controller redundancy, is to download the
same configuration to both IO Controllers, thereby creating an IP address conflict as
well as duplicating the symbolic name. This should be avoided.
network.
PROFINET Scan Tool (for assigning the IO Device names) can only
operate when connected to the Ethernet network.
files and DTMs for the connected IO Devices.
the CJ1W-PROFINET IO Controller DTM. Give the detected IO Devices an
appropriate name according to their position and /or function. It is possible
to give a IO device a temporary IP-address but it will be set/changed later
by the IO Controller.
the communication parameters to connect to the IO Controller:
Tree of the network by dragging and dropping from the Device Catalogue.
Assign the I/O modules for each individual IO Device. Use the exact names
given to the IO devices with the network scan tool. Make sure that the IP
address for each item on the network is unique.
status of the Unit.
Set an IP address in the PROFINET IO Controller by using the Network
Scan View.
Enter the same IP address in the DTM.
Confirm the on-line connection by putting the DTM on-line.
Set the PROFINET Names of the PROFINET IO Devices by using the
Network Scan View.
Section 3-4
27