Troubleshooting using the IO Controller indicators
6-2-3-4 Memory access errors
Special Unit error
Memory access error
6-2-3-5 CPU Unit exchange
Backplane Bus error
7-segment
--
7-segment
E9
7-segment
H0
MS indicator
ON (red)
MS indicator
ON (red)
MS indicator
Flashing (red)
/i
Likely cause
The PROFINET IO controller encountered an internal error and can not
continue.
IO Controller Unit response
The Unit will stop processing. Records the error in the errorlog.
CIO Area Flags allocated to the IO Controller Unit
None of the bits is set.
Correction
Restart the IO Controller. Replace the IO-Controller if the error recurs.
/i
Likely cause
The PROFINET lO Controller encountered accessing its internal memory.
IO Controller Unit response
The Unit will stop processing. Records the error in the errorlog.
CIO Area Flags allocated to the IO Controller Unit
None of the bits is set.
Correction
Restart the IO Controller. Replace the IO-Controller if the error recurs.
/i
Likely cause
The PROFINET IO controller encountered an error while aceesing the
backplane bus of the PLC.
IO Controller Unit response
The Unit will stop processing. Records the error in the errorlog.
CIO Area Flags allocated to the IO Controller Unit
None of the bits is set.
Correction
Restart the PLC. Check the PLC for faults in the backplane bus. Replace the
IO-Controller or other Units if the error recurs.
NS indicator
OFF
NS indicator
OFF
NS indicator
OFF
Error log (Hex)
0601
Error log (Hex)
0602
Error log (Hex)
000E
Section 6-2